2
3. Remove the screws that secure the main control
board and terminal strip assembly inside of the
control panel.
4.
Lay the panel horizontal inside of the control box to
allow for room to install the heat kit. See Figure 3.
Installation
1. Disconnect power to the VVC* unit.
2. Remove the blower access panel and top panel.
See Figure 1.
Figure 1. Remove Blower Access Panel and Top Panel
5. Prepare the
transformer and relay assembly for
installation. Figure 4 shows the transformer
and relay assembly.
6. The transformer is factory-wired for 240V. No
changes are necessary for 240V applications.
For 208V applications, remove the red lead from
the 240V terminal and connect it to the 208V
terminal on the transformer. See Figure 5.
Figure 3. Reposition Control Board Assembly
Figure 4. Transformer and Relay Assembly
Figure 2. Remove Control Board Assembly Screws
Figure 5. Select 240V or 208V Terminal on Transformer
240V
Terminal
208V
Terminal
IMPORTANT!
This heat kit includes a transformer and relay
assembly. The transformer is factory-wired for
240V. For 208V, remove the red lead from the 240V
terminal and connect it to the 208V terminal on the
transformer. See step 6.
Failure to connect to the appropriate terminal can
cause the heat assembly to not operate properly.