Unit Start­Up

Figure 21. Break Out Circuit Breaker Knockout

1.  Check that all electrical connections have been 

completed and jumpers configured (if required).

2.  Break out appropriate area of the circuit breaker 

knockout on the blower access panel. See Figure 20.  

NOTE - 

For  V8EH0050P-1P, V8EH0080P-1P and 

V8EH0100P-1P, remove only the left knockout.

Circuit Breaker 

Knockout

3.  Reinstall the blower access panel and top panel on 

the VVC* unit.

4.  Restore power to the unit.

Figure 22. Completed Installation

5.  If using a local controller, set the setpoint above 

room temperature to signal a call for heat.

6. 

Confirm new Heater kit has been engaged. 

7. 

Confirm that the total amp draw of the new heater 

kit does not exceed Minimum Circuit Ampacity for 

installed heater kit stated on unit nameplate or this 

manual. 

8. 

Confirm  expected  temperature  difference  exists  

between return air and supply air. 

9.  Adjust temperature setting on controller and 

confirm Heater kit completely disengages. 

10. 

Confirm  blower  continues  to  run  for  a  minimum 

period  of  time  if  the  system  is  turned  off  at  the 

controller when the heater kit is engaged. 

11. 

Remove the blower access panel. Affix the wiring 

diagram sticker to blower scroll, aligned with the 

unit wiring diagram sticker. 

12. Reinstall the blower access panel. Final installation 

shown in Figure 22.

13. Set the local controller to the desired setting.

Summary of Contents for V8EH-1P Series

Page 1: ...valent using factory specified parts Do not use this system if any part has been under water A flood damaged appliance is extremely dan gerous Immediately call a licensed professional HVAC service tec...

Page 2: ...for 240V No changes are necessary for 240V applications For 208V applications remove the red lead from the 240V terminal and connect it to the 208V terminal on the transformer See Figure 5 Figure 3 R...

Page 3: ...terminal to L1 and connect the black wire spade terminal to L2 on the VVC terminal block See Figures 8 and 9 Figure 8 Connect Heat Kit to L1 L2 Figure 10 VVCA H4 1P Connect Heat Kit to CN 14 10 Connec...

Page 4: ...e heating elements must be inserted into the holes in the back of the VVCA unit See Figure 14 17 Secure the circuit breaker panel onto the lip at the front of the control box with the two short screws...

Page 5: ...clamp already in the VVC control box to secure the wires See Figure 18 Figure 20 Connect Electrical Power 19 Connect the white plug of the breaker panel to the white connector of the transformer and...

Page 6: ...heat 6 Confirm new Heater kit has been engaged 7 Confirm that the total amp draw of the new heater kit does not exceed Minimum Circuit Ampacity for installed heater kit stated on unit nameplate or thi...

Page 7: ...30 230 4 6 15 700 3 0 28 8 30 240 5 0 17 100 3 0 29 8 30 7 5 kW V8EH0080P 1P 13P63 208 5 6 19 200 3 0 37 8 40 220 6 3 21 500 3 0 39 8 40 230 6 9 23 500 3 0 41 8 45 240 7 5 25 600 3 0 42 8 45 10 kW V8E...

Page 8: ...it Ampacity includes the Blower Motor Full Load Amps 1 Electric heater capacity only does not include additional blower motor heat capacity 2 Refer to National or Canadian Electrical Code manual to de...

Page 9: ...ermine at what outside ambient temperature the heat kit is to turn on and what outside ambient temperature the heat kit is to turn off See Figure 24 Electrical Data VVCB 3P VVCB012H4 Description Input...

Page 10: ...8 30 240 5 0 17 100 3 0 29 8 30 7 5 kW V8EH0080P 1P 13P63 208 5 6 19 200 3 0 37 8 4 40 5 220 6 3 21 500 3 0 39 8 4 40 5 230 6 9 23 500 3 0 41 8 45 5 240 7 5 25 600 3 0 42 8 45 5 10 kW V8EH0100P 1P 13P...

Page 11: ...4 80 6 220 12 6 43 000 4 2 53 3 24 1 60 4 30 77 4 80 6 230 13 8 47 000 4 2 55 3 25 1 60 4 30 80 4 90 6 240 15 0 51 000 4 2 57 3 26 1 60 30 83 4 90 6 20 kW V8EH0200P 1P 13P76 208 15 0 51 200 4 2 50 3...

Page 12: ...2 4 45 220 6 3 21 500 5 7 43 2 45 230 6 9 23 500 5 7 44 2 45 240 7 5 25 600 5 7 46 2 50 10 kW V8EH0100P 1P 13P64 208 7 5 25 600 5 7 52 3 60 220 8 4 28 700 5 7 55 3 60 230 9 2 31 400 5 7 57 3 60 240 10...

Page 13: ...90 6 240 15 0 51 000 6 0 59 6 26 1 60 30 85 7 90 6 20 kW V8EH0200P 1P 13P76 208 15 0 51 200 6 0 52 6 45 1 60 4 50 97 7 100 6 220 16 8 57 300 6 0 55 6 48 1 60 4 50 103 7 110 6 230 18 4 62 700 6 0 57 6...

Page 14: ...L2 XT1 C N50 CN51 RY1 RY2 RY3 RY4 1 2 3 4 5 6 HTON AUXH Figure 25 V8EH0050P 1P 5kW Wiring Diagram Figure 26 V8EH0080P 1P 7 5 and V8EH0100P 1P 10kW Wiring Diagram 1 2 3 4 5 6 1 2 3 4 5 6 L1 L2 XT1 CN5...

Page 15: ...8EH0150P 1P 15kW Wiring Diagram 1 2 3 4 5 6 1 2 3 4 5 6 L1 L2 XT1 CN50 CN51 RY1 RY2 RY3 RY4 HTON AUXH Figure 28 V8EH0200P 1P 20kW Wiring Diagram L1 L2 XT1 1 2 3 4 5 6 1 2 3 4 5 6 CN50 CN51 RY1 RY2 RY3...

Page 16: ...16 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Reviews: