13
VVCB60H4
Description
Input
Blower
Motor
Full
Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
5
Single Point
Power Source
Blower Speed
Volt kW
1
Btuh
Ckt 1 Ckt 2 Ckt 1 Ckt 2
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Low Medium High
5 kW
V8EH0050P-1P
(
13P59
)
208
3.8
12,800
6.0
30.5 - - -
4
35
- - -
- - -
- - -
•
•
•
220
4.2
14,300
6.0
31.5 - - -
4
35
- - -
- - -
- - -
•
•
•
230
4.6
15,700
6.0
32.5 - - -
35
- - -
- - -
- - -
•
•
•
240
5.0
17,100
6.0
33.5 - - -
35
- - -
- - -
- - -
•
•
•
7.5 kW
V8EH0080P-1P
(
13P63
)
208
5.6
19,200
6.0
41.6 - - -
4
45
- - -
- - -
- - -
•
•
•
220
6.3
21,500
6.0
43.6 - - -
45
- - -
- - -
- - -
•
•
•
230
6.9
23,500
6.0
44.6 - - -
45
- - -
- - -
- - -
•
•
•
240
7.5
25,600
6.0
46.6 - - -
50
- - -
- - -
- - -
•
•
•
10 kW
V8EH0100P-1P
(
13P64
)
208
7.5
25,600
6.0
52.6 - - -
60
- - -
- - -
- - -
•
•
•
220
8.4
28,700
6.0
55.6 - - -
60
- - -
- - -
- - -
•
•
•
230
9.2
31,400
6.0
57.6 - - -
60
- - -
- - -
- - -
•
•
•
240 10.0 34,100
6.0
59.6 - - -
60
- - -
- - -
- - -
•
•
•
15 kW
V8EH0150P-1P
(
13P75
)
208 11.3 38,400
6.0
52.6 23.1
60
4
30
75.7
80
6
- - -
•
•
220 12.6 43,000
6.0
55.6 24.1
60
4
30
79.7
80
6
- - -
•
•
230 13.8 47,000
6.0
57.6 25.1
60
4
30
82.7
90
6
- - -
•
•
240 15.0 51,000
6.0
59.6 26.1
60
30
85.7
90
6
- - -
•
•
20 kW
V8EH0200P-1P
(
13P76
)
208 15.0 51,200
6.0
52.6 45.1
60
4
50
97.7
100
6
- - -
•
•
220 16.8 57,300
6.0
55.6 48.1
60
4
50
103.7
110
6
- - -
•
•
230 18.4 62,700
6.0
57.6 50.1
60
4
60
107.7
110
6
- - -
•
•
240 20.0 68,200
6.0
59.6 52.1
60
60
111.7
125
6
- - -
•
•
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Electric heat is rated at 240V. If voltage is less than 240V installer must supply different circuit breaker as shown in the tables. Installer must also size wiring based on
reduced voltage for proper installation.
5
Single point power source breaker for unit with 15 and 20 kW electric heat is not furnished and must be field provided.
6
Do not operate fan on low speed when V8EH Electric Heat Kit is used with VVC* air handler.