8
VVCA048H4, VVCA054H4
Description
Input
Blower
Motor
Full
Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
⁵Single Point
Power Source
Blower Speed
Volt kW
1
Btuh
Ckt 1 Ckt 2 Ckt 1 Ckt 2
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Low Medium High
5 kW
V8EH0050P-1P
(
13P59
)
208
3.8 12,800
4.2
28.3 - - -
⁴30
- - -
- - -
- - -
•
•
•
220
4.2 14,300
4.2
29.3 - - -
⁴30
- - -
- - -
- - -
•
•
•
230
4.6 15,700
4.2
30.3 - - -
35
- - -
- - -
- - -
•
•
•
240
5.0 17,100
4.2
31.3 - - -
35
- - -
- - -
- - -
•
•
•
7.5 kW
V8EH0080P-1P
(
13P63
)
208
5.6 19,200
4.2
39.3 - - -
⁴40
- - -
- - -
- - -
•
•
•
220
6.3 21,500
4.2
41.3 - - -
45
- - -
- - -
- - -
•
•
•
230
6.9 23,500
4.2
42.3 - - -
45
- - -
- - -
- - -
•
•
•
240
7.5 25,600
4.2
44.3 - - -
45
- - -
- - -
- - -
•
•
•
10 kW
V8EH0100P-1P
(
13P64
)
208
7.5 25,600
4.2
50.3 - - -
60
- - -
- - -
- - -
•
•
•
220
8.4 28,700
4.2
53.3 - - -
60
- - -
- - -
- - -
•
•
•
230
9.2 31,400
4.2
55.3 - - -
60
- - -
- - -
- - -
•
•
•
240 10.0 34,100
4.2
573
- - -
60
- - -
- - -
- - -
•
•
•
15 kW
V8EH0150P-1P
(
13P75
)
208 11.3 38,400
4.2
50.3
23
60
⁴25
73.3
80
⁶- - -
•
•
220 12.6 43,000
4.2
53.3
24
60
⁴25
77.3
80
⁶- - -
•
•
230 13.8 47,000
4.2
55.3
25
60
⁴25
80.3
90
⁶- - -
•
•
240 15.0 51,000
4.2
57.3
26
60
30
83.3
90
⁶- - -
•
•
20 kW
V8EH0200P-1P
(
13P76
)
208 15.0 51,200
4.2
50.3
45
60
⁴50
95.3
100
⁶- - -
•
•
220 16.8 57,300
4.2
53.3
48
60
⁴50
101.3
110
⁶- - -
•
•
230 18.4 62,700
4.2
55.3
50
60
⁴50
105.3
110
⁶- - -
•
•
240 20.0 68,200
4.2
57.3
52
60
60
109.3
110
⁶- - -
•
•
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Electric heat is rated at 240V. If voltage is less than 240V installer must supply different circuit breaker as shown in the tables. Installer must also size wiring based on
reduced voltage for proper installation.
5
Single point power source breaker for unit with 15 and 20 kW electric heat is not furnished and must be field provided.
6
Do not operate fan on low speed when V8EH Electric Heat Kit is used with VVC* air handler.
VVCA036H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Volt kW
1
Btuh
Low Medium High
5 kW
V8EH0050P-1P (
13P59
) 208
3.8
12,800
4.2
28.3
⁴30
•
•
•
220
4.2
14,300
4.2
29.3
⁴30
•
•
•
230
4.6
15,700
4.2
30.3
35
•
•
•
240
5.0
17,100
4.2
31.3
35
•
•
•
7.5 kW
V8EH0080P-1P (
13P63
) 208
5.6
19,200
4.2
39.3
⁴40
•
•
•
220
6.3
21,500
4.2
41.3
45
•
•
•
230
6.9
23,500
4.2
42.3
45
•
•
•
240
7.5
25,600
4.2
44.3
45
•
•
•
10 kW
V8EH0100P-1P (
13P64
) 208
7.5
25,600
4.2
50.3
60
⁶- - -
•
•
220
8.4
28,700
4.2
53.3
60
⁶- - -
•
•
230
9.2
31,400
4.2
55.3
60
⁶- - -
•
•
240 10.0 34,100
4.2
57.3
60
⁶- - -
•
•