BLOWER DATA
SLP99UH070XV36B BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
471
519
614
709
805
900
996
1091
Increase (+7.5%) Heat CFM
435
480
570
660
751
841
931
1021
Default Heat CFM
399
441
526
611
696
781
866
951
Decrease (-7.5% ) Heat CFM
369
408
486
564
643
721
799
877
Decrease (-15% ) Heat CFM
339
375
446
517
589
660
732
803
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
595
715
815
950
855
1045
1205
1350
Default Cool CFM
520
655
755
840
790
945
1090
1255
Decrease (-10%) Cool CFM
490
595
670
745
720
845
985
1130
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 250 cfm.