Page 10
BLOWER DATA
SLP99UH090XV48C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
769
835
968
1101
1234
1367
1500
1633
Increase (+7.5%) Heat CFM
713
776
902
1028
1155
1281
1407
1534
Default Heat CFM
656
716
836
955
1075
1195
1314
1434
Decrease (-7.5% ) Heat CFM
595
652
767
882
997
1112
1227
1342
Decrease (-15% ) Heat CFM
534
589
699
809
919
1029
1139
1249
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
840
1005
1155
1315
1165
1375
1580
1770
Default Cool CFM
780
915
1045
1190
1075
1265
1440
1645
Decrease (-10%) Cool CFM
690
835
955
1070
935
1145
1320
1465
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.