BLOWER DATA
SLP99UH135XV60D BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
− Air volumes in
bold
require Optional Return Air Base and
field fabricated transition to accommodate
20 x 25 x 1 in. air filter in order to maintain proper air velocity.
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
927
1010
1175
1340
1505
1671
1836
2001
Increase (+7.5%) Heat CFM
844
923
1081
1239
1398
1556
1714
1873
Default Heat CFM
760
836
987
1138
1290
1441
1593
1744
Decrease (-7.5% ) Heat CFM
703
775
919
1064
1208
1352
1496
1641
Decrease (-15% ) Heat CFM
646
715
852
989
1126
1263
1400
1537
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
1070
1235
1385
1535
1550
1720
1925
2005
Default Cool CFM
985
1110
1245
1395
1415
1605
1755
1970
Decrease (-10%) Cool CFM
870
1010
1110
1260
1280
1435
1610
1755
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.