Page 16
BLOWER DATA
SLP99UH110XV60C BLOWER PERFORMANCE (less filter)
SINGLE SIDE RETURN AIR
− Air volumes in
bold
require Optional Return Air Base and
field fabricated transition to accommodate
20 x 25 x 1 in. air filter in order to maintain proper air velocity.
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
733
825
1009
1194
1378
1562
1747
1931
Increase (+7.5%) Heat CFM
708
794
967
1139
1312
1484
1657
1829
Default Heat CFM
683
763
924
1085
1245
1406
1566
1727
Decrease (-7.5% ) Heat CFM
632
707
857
1007
1157
1307
1457
1608
Decrease (-15% ) Heat CFM
580
650
790
929
1069
1209
1348
1488
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
1050
1195
1315
1495
1515
1710
1870
2065
Default Cool CFM
960
1095
1220
1355
1360
1555
1755
1890
Decrease (-10%) Cool CFM
850
985
1095
1220
1215
1400
1555
1755
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between.
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position.
minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.