IOM – FLEXY II – 1007 – E
Page 92
Moisture or contaminants in the system
If the circuit pressure is higher (<1bar) than the
saturated pressure corresponding to the
measured outdoor temperature, there is
possibility that some contaminants are present in
the system.
Reclaim the ref rigerant, and vacuum the circuit
(Ensure v ery low and slow vacuum for R407c)
Recharge the unit
Condenser coil is obstructed
Check the condenser coil and clean is necessary
HP PROBLEMS AND
HP CUT OUTS
Recycled Hot Air
Check clearance around the condenser
Incorrect adjustment of the expansion valv e
Low ref rigerant charge
Strong v ariations of
pressure ( 2 to 3 bar)
Thermostatic
Expansion Valve
"hunting"
Filter drier obstructed with gas bubbles at the
expansion valv e inlet
Moisture in the system
Ref er to LP problems and LP cut out section
Very high superheat, very hot compressor
Open the superheat adjustment on the expansion
v alve.
Check the pressure drop on the filter drier in the
suction line
Very high discharge
temperature,
High amps measured
at compressor
Four Way reversing v alve possibly blocked,
abnormal noise f rom the valv e, low LP and
increasing HP
Check operation of the v alve by going through
cy cle inv ersions. Change if necessary.
Ref er to LP problems
INDOOR FAN BLOWER
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
High amps on action
Fan motor
Pressure drop in the ducting installation too low.
Reduce the rotation speed of the f an
Measure and estimate the airflow and pressure
and compare with the specification from
customer.
High amps on reaction
Fan motor
Pressure drop in the ducting installation too high.
Reduce the rotation speed of the f an
Measure and estimate the airflow and pressure
and compare with the specification from
customer.
Unstable running and
high v ibration
Fan jumping f rom one operating point to the
other
Change rotation speed of the fan.
OUTDOOR AXI AL FAN
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
High Amps due to a low voltage f rom the main
supply
Check the v oltage drop when all components are
running.
Change the circuit breaker f or one with a higher
rating.
High amps due to f reezing of the coil
Check the adjustable amps on the motor starter.
Adjust the defrost cycle set points.
Heat Pump mode:
Circuit breaker open
Flexy: Water ingress in the motor connection
box.
Change the component
MAINTENANCE DIAGNOSTIC
Summary of Contents for ROOFTOP FLEXY FXK 100
Page 2: ......
Page 11: ...IOM FLEXY II 1007 E Page 9 COMMENTS COMMISSIONING REPORT...
Page 41: ...IOM FLEXY II 1007 E Page 39 VENTILATION AIRFLOW BALANCING AT18 18S...
Page 42: ...IOM FLEXY II 1007 E Page 40 VENTILATION AIRFLOW BALANCING ADH355L...
Page 43: ...IOM FLEXY II 1007 E Page 41 VENTILATION AIRFLOW BALANCING ADH450L...
Page 44: ...IOM FLEXY II 1007 E Page 42 VENTILATION AIRFLOW BALANCING ADH500L...
Page 60: ...IOM FLEXY II 1007 E Page 58 60kW 120kW HEATING GAS BURNER...
Page 61: ...IOM FLEXY II 1007 E Page 59 180kW 240kW HEATING GAS BURNER...
Page 68: ...IOM FLEXY II 1007 E Page 66 60kW 120kW HEATING MODULATING GAS BURNER...
Page 69: ...IOM FLEXY II 1007 E Page 67 180kW 240kW HEATING MODULATING GAS BURNER...
Page 74: ...IOM FLEXY II 1007 E Page 72 CLIMATIC 50 CONTROLER ELECTRICAL DATA WIRING DIAGRAMS...
Page 75: ...IOM FLEXY II 1007 E Page 73 CLIMATIC 50 INPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Page 76: ...IOM FLEXY II 1007 E Page 74 CLIMATIC 50 OUTPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Page 77: ...IOM FLEXY II 1007 E Page 75 DAD SMOKE DETECTOR ELECTRICAL DATA WIRING DIAGRAMS...
Page 78: ...IOM FLEXY II 1007 E Page 76 GENERAL CUSTOMER CONNECTION TCB ELECTRICAL DATA WIRING DIAGRAMS...
Page 81: ...IOM FLEXY II 1007 E Page 79 WIRING DIAGRAM GAS BURNER 120kW ELECTRICAL DATA WIRING DIAGRAMS...
Page 83: ...IOM FLEXY II 1007 E Page 81 WIRING DIAGRAM ELECTRIC HEATER ELECTRICAL DATA WIRING DIAGRAMS...
Page 89: ...IOM FLEXY II 1007 E Page 87 FCM 150 FHM 150 PRINCIPLE SKETCHES...
Page 90: ...IOM FLEXY II 1007 E Page 88 FCM 170 FHM 170 PRINCIPLE SKETCHES...
Page 91: ...IOM FLEXY II 1007 E Page 89 FCM 200 230 FHM 200 230 PRINCIPLE SKETCHES...
Page 100: ...IOM FLEXY II 1007 E Page 98 LONGVIC SITE ISO 9001 2000 CERTIFICATE...
Page 101: ...IOM FLEXY II 1007 E Page 99 EC CONFORMITY DECLARATION...
Page 102: ...IOM FLEXY II 1007 E Page 100 DAD LOTUS CERTIFICATE...
Page 103: ...IOM FLEXY II 1007 E Page 101 GLASS WOOL INSULATION CERTIFICATE...
Page 104: ...IOM FLEXY II 1007 E Page 102 GLASS WOOL INSULATION CERTIFICATE...
Page 105: ...IOM FLEXY II 1007 E Page 103 F7 FILTER INSULATION CERTIFICATE...
Page 106: ...IOM FLEXY II 1007 E Page 104 G4 FILTER INSULATION CERTIFICATE...
Page 107: ...IOM FLEXY II 1007 E Page 105 FLEXY 60 120 180 240 KW GAS BURNER CERTIFICATE...
Page 108: ...IOM FLEXY II 1007 E Page 106 ROOFTOP PED CONFORMITY CERTIFICATE...
Page 109: ...IOM FLEXY II 1007 E Page 107 ROOFTOP PED CONFORMITY CERTIFICATE...