IOM – FLEXY II – 1007 – E
Page 33
BELT
TENSION
On deliv ery, the driv e belts are new and correctly
tensioned. After the first 50 operating hours check and
adjust the tension. 80% of the total elongation of belts is
generally produced during the first 15 hours of operation.
Bef ore adjusting the tension, make sure that the pulleys
are correctly aligned.
To tension the belt, set the height of motor support plate
by moving the plate adjustment screws.
The recommended def lection is 20 mm per meter from
centre to centre.
Check that according to the diagram below (f igure 12), the
f ollowing ratio remains the same.
The belts should alway s be replaced when:
- The disk is set to maximum,
- The belt rubber is worn or the wire is visible.
Replacement belts must hav e the same rated size as the
ones they are replacing. If a transmission system has
sev eral belts, they must all be f rom the same
NOTE:
An under-tensioned belt will slip, heat and wear
prematurely. On the other hand, if a belt is over-tensioned,
the pressure on the bearings will cause them to over-heat
and wear prematurely. Incorrect alignment will also cause
the belts to wear prematurely.
VENTILATION : BELT TENSION
Fig. 12
Summary of Contents for ROOFTOP FLEXY FXK 100
Page 2: ......
Page 11: ...IOM FLEXY II 1007 E Page 9 COMMENTS COMMISSIONING REPORT...
Page 41: ...IOM FLEXY II 1007 E Page 39 VENTILATION AIRFLOW BALANCING AT18 18S...
Page 42: ...IOM FLEXY II 1007 E Page 40 VENTILATION AIRFLOW BALANCING ADH355L...
Page 43: ...IOM FLEXY II 1007 E Page 41 VENTILATION AIRFLOW BALANCING ADH450L...
Page 44: ...IOM FLEXY II 1007 E Page 42 VENTILATION AIRFLOW BALANCING ADH500L...
Page 60: ...IOM FLEXY II 1007 E Page 58 60kW 120kW HEATING GAS BURNER...
Page 61: ...IOM FLEXY II 1007 E Page 59 180kW 240kW HEATING GAS BURNER...
Page 68: ...IOM FLEXY II 1007 E Page 66 60kW 120kW HEATING MODULATING GAS BURNER...
Page 69: ...IOM FLEXY II 1007 E Page 67 180kW 240kW HEATING MODULATING GAS BURNER...
Page 74: ...IOM FLEXY II 1007 E Page 72 CLIMATIC 50 CONTROLER ELECTRICAL DATA WIRING DIAGRAMS...
Page 75: ...IOM FLEXY II 1007 E Page 73 CLIMATIC 50 INPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Page 76: ...IOM FLEXY II 1007 E Page 74 CLIMATIC 50 OUTPUT FCM FHM FGM FDM ELECTRICAL DATA WIRING DIAGRAMS...
Page 77: ...IOM FLEXY II 1007 E Page 75 DAD SMOKE DETECTOR ELECTRICAL DATA WIRING DIAGRAMS...
Page 78: ...IOM FLEXY II 1007 E Page 76 GENERAL CUSTOMER CONNECTION TCB ELECTRICAL DATA WIRING DIAGRAMS...
Page 81: ...IOM FLEXY II 1007 E Page 79 WIRING DIAGRAM GAS BURNER 120kW ELECTRICAL DATA WIRING DIAGRAMS...
Page 83: ...IOM FLEXY II 1007 E Page 81 WIRING DIAGRAM ELECTRIC HEATER ELECTRICAL DATA WIRING DIAGRAMS...
Page 89: ...IOM FLEXY II 1007 E Page 87 FCM 150 FHM 150 PRINCIPLE SKETCHES...
Page 90: ...IOM FLEXY II 1007 E Page 88 FCM 170 FHM 170 PRINCIPLE SKETCHES...
Page 91: ...IOM FLEXY II 1007 E Page 89 FCM 200 230 FHM 200 230 PRINCIPLE SKETCHES...
Page 100: ...IOM FLEXY II 1007 E Page 98 LONGVIC SITE ISO 9001 2000 CERTIFICATE...
Page 101: ...IOM FLEXY II 1007 E Page 99 EC CONFORMITY DECLARATION...
Page 102: ...IOM FLEXY II 1007 E Page 100 DAD LOTUS CERTIFICATE...
Page 103: ...IOM FLEXY II 1007 E Page 101 GLASS WOOL INSULATION CERTIFICATE...
Page 104: ...IOM FLEXY II 1007 E Page 102 GLASS WOOL INSULATION CERTIFICATE...
Page 105: ...IOM FLEXY II 1007 E Page 103 F7 FILTER INSULATION CERTIFICATE...
Page 106: ...IOM FLEXY II 1007 E Page 104 G4 FILTER INSULATION CERTIFICATE...
Page 107: ...IOM FLEXY II 1007 E Page 105 FLEXY 60 120 180 240 KW GAS BURNER CERTIFICATE...
Page 108: ...IOM FLEXY II 1007 E Page 106 ROOFTOP PED CONFORMITY CERTIFICATE...
Page 109: ...IOM FLEXY II 1007 E Page 107 ROOFTOP PED CONFORMITY CERTIFICATE...