147
Error Code:
P2
Description:
Compressor top high temperature protection (OLP)
General Note:
If the sampling voltage is not 5V, the LED will display the P2 error code.
P2
Check the air flow system
of indoor and outdoor units.
Does a problem exist?
No
Clear air flow blockage.
Yes
Power off the unit and wait
10 minutes before restarting.
Yes
Check compressor
temperature. Is it within
acceptable parameters?
Check the overload
protector. Is it properly wired?
No
No
Yes
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the outdoor control PCB.
No
Replace the OLP.
Ensure a proper connection.
Yes
Error Code:
P3
Description:
Outdoor unit low temperature lockout.
General Note:
The outdoor unit will lockout if when in heating mode, when the outdoor temperature is lower than -13°F (-25°C) for 1 hour,
the indoor unit display error code.
The outdoor unit will resume operation when either:
The OUTDOOR temperature is higher than -7.6°F (-22°C) for 10 minutes and compressor has been stopped for 1 hour
or
Outdoor temperature is higher than 23°F (-5°C) for 10 minutes