
123
Error Code:
P4
Description:
High temperature sensed at compressor discharge line.
General Note:
When the compressor discharge temperature(T5) is more than 239°F (115°C) for 10 seconds, the compressor will stop and
restart till T5 is less than 194°F (90°C).
Temperature protection of compressor.
Check whether the compressor discharge temp. is
more than 239°F (115°C) ?
No
Check whether the connection is right between com
-
pressor discharge temp. sensor and PCB according to
wiring diagrams?
Check whether the
refrigerant is leak.
Yes
Stop leaking and add
refrigerant.
Yes
No
Correct the wiring connection.
No
Yes
Measure the resistance value of compressor dis
-
charge temp. sensor. If the value is not normal is
normal refer to the Appendix 2?
Replace the compressor
discharge temp. sensor.
No
Yes
Replace outdoor main PCB.
No
Replace high pressure valve assy.
Summary of Contents for MWMA009S4-*L
Page 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Page 118: ...118 Error Code P1 continued ...
Page 120: ...120 Error Code P2 continued ...
Page 122: ...122 Error Code P3 continued ...
Page 144: ...144 Error Code P0 continued P U P V ...
Page 145: ...145 P W P N ...
Page 151: ...151 Error Code P6 continued ...