124
Error Code:
P5
Description:
High temperature sensed at outdoor coil.
General Note:
When outdoor pipe temperature is more than 149°F (65°C), the unit will stop, and unit runs again when outdoor pipe
temperature is less than 125.6°F (52°C).
High temperature protection of
condenser
Check whether the compressor
temperature is higher than 149°F
(65°C) ?
Is the connection be
-
tween the temperature
sensor and the PCB
correct?
No
Repair/replace wiring as
per wiring diagram.
No
Yes
Check the resistance
value of the outdoor
temperature sensor is
correct. Refer to table
Appendix 1.
Replace the temperature
sensor.
No
Yes
Yes
Check whether the outdoor ambi
-
ent temperature is higher than
122°F (50°C).
Switch unit off until ambient tem
-
perature is within normal operating
parameters.
Yes
No
Is there sufficient airflow across
outdoor unit coils?
Remove obstruction or increase
ventilation path/airflow.
No
Remove remaining refrigerant
charge, pressure test and locate
leak. Add correct charge. Test
system. If system fails to operate
correctly replace outdoor board.
Replace the outdoor main board.
Yes
Are the outdoor unit fans operat
-
ing correctly?
Refer to the fault code fan speed
malfunction (E8).
No
Yes
Are the outdoor unit coils clean?
Clean the outdoor coil thoroughly.
No
Yes
Confirm if system has the correct
refrigerant charge.
No
Yes
Summary of Contents for MWMA009S4-*L
Page 113: ...113 Error Code E6 continued Two terminals of the inductor Inductor ...
Page 118: ...118 Error Code P1 continued ...
Page 120: ...120 Error Code P2 continued ...
Page 122: ...122 Error Code P3 continued ...
Page 144: ...144 Error Code P0 continued P U P V ...
Page 145: ...145 P W P N ...
Page 151: ...151 Error Code P6 continued ...