background image

Page 11

New or Replacement Line Set

This section provides information on new installation or re-

placement of existing line set. If a new or replacement line 

set is not required, then proceed to Brazing Connections 

on page 13.
Field refrigerant piping consists of liquid and suction lines 

from the outdoor unit (braze connections) to the indoor 

unit  coil  (flare  or  braze  connections).  Use  Lennox  L15 

(braze,  non-flare)  series  line  set,  or  use  field-fabricated 

refrigerant lines as listed in table 2. 

TABLE 2 

REFRIGERANT LINE SET – INCHES (MM)

Model

Valve Field  

Connections

Recommended Line Set

Liquid  

Line

Suction  

Line

Liquid  

Line

Suction  

Line

L15 Line Sets

-036

3/8 in. 

(10 mm)

7/8 in. 

(22 mm)

3/8 in. 

(10 mm)

7/8 in. 

(22 mm)

L15-65 

15 ft. - 50 ft. 

(4.6 m - 15 m)

-042
-048

-060

3/8 in. 

(10 mm)

1-1/8 in. 

(28 mm)

3/8 in. 

(10 mm)

1-1/8 in. 

(28 mm) Field Fabricated

NOTE - Some applications may require a field-provided 7/8"

 to 

1-1/8

"

 adapter.

NOTE

 - 

When  installing  refrigerant  lines  longer  than  50 

feet, refer to the Refrigerant Piping Design and Fabrica

-

tion  Guidelines  manual  available  on  LennoxPros.com 

(Corp. 9351-L9), or contact the Technical Support Depart

-

ment Product Application group for assistance.

NOTE

 - 

For new or replacement line set installation, refer 

to Service and Application Note - Corp. 9112-L4 (C-91-4)

.

 WARNING

When using a high pressure gas such as 

nitrogen to pressurize a refrigeration or air 

conditioning system, use a regulator that can 

control the pressure down to 1 or 2 psig (6.9 

to 13.8 kPa).

 WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant 

must be used and recovered responsibly.
Failure to follow this warning may result in personal 

injury or death.

 WARNING

Fire, Explosion and Personal Safety hazard. 

Failure to follow this warning could result in 

damage, personal injury or death.
Never use oxygen to pressurize or purge 

refrigeration lines. Oxygen, when exposed 

to a spark or open flame, can cause fire and/

or an explosion, that could result in property 

damage, personal injury or death.

If refrigerant lines are routed through a wall, seal and 

isolate the opening so vibration is not transmitted to the 

building. Pay close attention to line set isolation during 

installation of any HVAC system. When properly isolated 

from building structures (walls, ceilings. floors), the refrig

-

erant lines will not create unnecessary vibration and sub-

sequent sounds.

The compressor is charged with sufficient Polyol ester oil 

for line set lengths up to 50 feet. Recommend adding oil to 

system based on the amount of refrigerant charge in the 

system. No need to add oil in a system with 20 pounds of 

refrigerant or less. For systems over 20 pounds - add one 

ounce for every five pounds of refrigerant over 20 pounds. 

Recommended topping-off POE oils are Mobil EAL ARC

-

TIC 22 CC or ICI EMKARATE RL32CF.

LIQUID LINE FILTER DRIER INSTALLATION

The filter drier (one is shipped with each ML14XC1 unit) 

must be field installed in the liquid line between the out

-

door unit's liquid line service valve and the indoor coil's 

metering device as illustrated in figure 6. This filter drier 

must be installed to ensure a clean, moisture-free sys-

tem. Failure to install the filter drier will void the warranty. 

A  replacement  filter  drier  is  available  from  Lennox.  See 

Brazing Connections on page  for special procedures on 

brazing filter drier connections to the liquid line.

OUTDOOR

UNIT

LIQUID LINE

SERVICE VALVE

LIQUID LINE

FILTER DRIER

LINE

LIQUID

LINE

BRAZE CONNECTION POINTS

FIGURE 6. Typical Liquid Line Filter Drier  

Installation  

Summary of Contents for ML14XC1 Series

Page 1: ...d Service Valves 6 Installation 8 Unit Placement 8 Removing and Installing Louvered Panels 10 New or Replacement Line Set 11 Brazing Connections 13 Flushing Line Set and Indoor Coil 16 Installing Indo...

Page 2: ...Hz J voltage Product Tier ML Merit Series Unit Type C Air Conditioner Cooling Stages 1 Single Stage Compressor Ratings Revision Level Nominal Cooling Capacity 036 3 tons 042 3 5 tons 048 4 tons 060 5...

Page 3: ...diameter in 5 16 5 16 5 16 5 16 No of rows 2 2 2 2 Fins per inch 22 22 22 22 Outdoor Fan Diameter in 22 22 22 26 No of Blades 3 3 4 4 Motor hp 1 6 1 6 1 4 1 4 Cfm 3160 3050 3600 4550 Rpm 825 825 825 8...

Page 4: ...CONNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4...

Page 5: ...CTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH S4 COMPRESSOR HARNESS TYPICAL PLUMBING COPELAND COMPRESSOR TYPICAL PLUMBING LG COMPRESSOR HIGH PRESSURE SWITCH S4 FIELD...

Page 6: ...p before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2 NM Machine screws 10 28 ft lb 3 NM Compressor bolts 90 in lb 10 N...

Page 7: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 8: ...ions If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be con structed Size barrier at least the same height and width as outdoor unit Mount barrier 24 inches 610...

Page 9: ...or 2 inches per 5 feet 50 mm per 1 5 m away from building structure DETAIL A DETAIL B INSTALL UNIT AWAY FROM WINDOWS TWO 90 ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION GROUND LEVEL MOU...

Page 10: ...Remove panel A first then B C and finally D When reinstalling panels reverse that order starting with panel D C B and finally A REMOVAL Repeat steps 1 2 and 3 to remove panels B C and D STEP 1 Startin...

Page 11: ...ING Fire Explosion and Personal Safety hazard Failure to follow this warning could result in damage personal injury or death Never use oxygen to pressurize or purge refrigeration lines Oxygen when exp...

Page 12: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 13: ...T Allow braze joint to cool before removing the wet rag from the service valve Temperatures above 250 F can damage valve seals IMPORTANT Use silver alloy brazing rods with 5 minimum silver alloy for c...

Page 14: ...EN HIGH LOW B A C PIPING PANEL REMOVAL AND LINE SET PREPARATION CAP AND CORE REMOVAL Remove piping panel for easier access to service valves Cut ends of the refrigerant lines square free from nicks or...

Page 15: ...T TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service va...

Page 16: ...STING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 17: ...Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wre...

Page 18: ...KP SURE CLOSE THE VALVE ON THE HFC 410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE SET DISCONNECT THE HFC 410A CYLINDER C CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE...

Page 19: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 20: ...rams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage co...

Page 21: ...CONTROL WIRING NOTE Wire tie provides low voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits NOTE For proper voltages select thermostat wire...

Page 22: ...Page 22 FIGURE 15 Typical Factory Wiring G and Y Voltages...

Page 23: ...Page 23 FIGURE 16 Typical Factory Wiring J Voltage...

Page 24: ...he technician to check the following items These checks may only be con ducted by a licensed professional HVAC technician Outdoor Unit 1 Inspect component wiring for loose worn or damaged connections...

Page 25: ...technician will check the refrigerant charge per the charging sticker information on the outdoor unit 3 Verify that system total static pressure and airflow set tings are within specific operating par...

Page 26: ...high pressure switch is closed 3 K1 1 N O closes energizing compressor B1 and out door fan motor B4 4 Compressor B1 and outdoor fan motor B4 begin im mediate operation END OF COOLING DEMAND 5 Cooling...

Page 27: ...the unit is running Power must be within range shown on the nameplate 8 Check system for sufficient refrigerant by using the procedures that follow System Refrigerant This section outlines procedures...

Page 28: ...DRY BULB A AND WET BULB B DT IS THE INTERSECTING VALUE OF A AND B IN THE TABLE SEE TRIANGLE 2 FIND TEMPERATURE DROP ACROSS COIL MEASURE ING THE COIL A AND C TEMPERATURE DROP FORMULA TDROP A MINUS C F...

Page 29: ...ve refrigerant based upon line length BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressure...

Page 30: ...26 9 80 26 7 235 15 26 1 31 7 85 29 4 254 10 23 3 36 8 90 32 2 274 5 20 6 42 5 95 35 0 295 0 17 8 48 6 100 37 8 317 5 15 0 55 2 105 40 6 340 10 12 2 62 3 110 43 3 365 15 9 4 70 0 115 46 1 391 20 6 7...

Reviews: