Page 21
ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING
HIGH VOLTAGE
FIELD WIRING
LOW VOLTAGE
FIELD WIRING
FACTORY
WIRING
WIRE RUN LENGTH
AWG# INSULATION TYPE
LESS THAN 100' (30 METERS)
18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
Install low voltage wiring from outdoor to indoor unit and from
thermostat to indoor unit as illustrated.
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and
secured away from any low voltage field wiring. To facilitate a
conduit, a cutout is located in the bottom of the control panel.
Connect conduit to the control panel using a proper conduit
fitting.
CONTROL WIRING
NOTE — Wire tie provides low voltage control wire strain relief and to maintain
separation of field installed low and high voltage circuits.
NOTE — For proper voltages, select thermostat wire (control wires) gauge per
table below
.
NOTE — Do not bundle any excess 24VAC control wires inside control panel.
A
Run 24VAC control wires through hole with grommet and secure
with provided wire tie.
B
Make 24VAC thermostat wire connections. Locate the two wires
from the contactor and make connection using field provided wire
nuts:
Yellow to Y1
Black to C (common)
W1
Y
G
C
R
Y
G
C
THERMOSTAT
INDOOR UNIT
POWER
HEAT
COOLING
INDOOR
BLOWER
COMMON
OUTDOOR
UNIT
Y1
C
W
R
THREE PHASE
CONTROL
WIRING
HIGH VOLTAGE
CONNECTIONS
(CONTACTOR)
GROUND
GROMMET
AND WIRE TIE
HIGH VOLTAGE
FLEXIBLE CONDUIT
A
B
CAPACITOR
WIRE
NUTS
FIGURE 14. Typical Wiring