INNOV@ CENT -AGU-0912-E
.
12
.
The following steps should be carried out to ensure proper installation:
D
Apply a anti-vibration rubber lining between the unit and the bottom.
D
Positioning the unit on the floor / base frame.
D
Further info to be added.
The recommended sizes for the power cables and emergency line are shown in the tables below:
Tab. 4 Electrical connections (INNOV@DM “CW”)
R (Radial)
C (Centrifugal)
Model
Power supply
Cable type
(*)
Power supply
Cable type
(*)
DMCDC0080
230V / 1Ph / 50Hz
4 x 6 mm
2
+ T 6 mm
2
230V / 1Ph / 50Hz
4 x 6 mm
2
+ T 6 mm
2
DMCDC0110
DMCDC0140
4 x 10 mm
2
+ T 6 mm
2
DMCDC0160
4 x 10 mm
2
+ T 6 mm
2
DMCDC0200
DMCDC0230
Tab. 5 Electrical connections (INNOV@DM “DX”)
R (Radial)
C (Centrifugal)
Model
Power supply
Cable type
(*)
Power supply
Cable type
(*)
DMADC0060
400V / 3Ph + N /
50Hz
4 x 6 mm
2
+ T 6 mm
2
400V / 3Ph + N / 50Hz
4 x 6 mm
2
+ T 6 mm
2
DMADC0080
DMADC0100
4 x 10 mm
2
+ T 6 mm
2
4 x 10 mm
2
+ T 6 mm
2
DMADC0110
DMADC0130
DMADC0160
4 x 16 mm
2
+ T 6 mm
2
4 x 16 mm
2
+ T 6 mm
2
DMADC0190
DMADC0205
(*) Sections dimensioned for using cables made with PVC, line max. lenght = 100m
Summary of Contents for INNOV DM R Series
Page 2: ......
Page 32: ......
Page 49: ...INNOV ECFAN DHR AGU 0912 E 17 6 Operating Diagrams DISPLACEMENT DOWNFLOW UPFLOW...
Page 76: ......