INNOV@ ECFAN DMR -AGU-0912-E
•
6
•
1.4 “CW” units hydraulic section
3-way valve
The 3-way valve used on INNOV@DM-R CW version units for inlet water flow regulation allowing a foundamentally
maximum precision’s regulation on CCAC applications.
Tab. 3 Technical characteristics
Frame 1
Frame 2
Frame 3
Brand / valve’s type
Controls VMT2
Controls VMT2
Controls VMBT3
Kvs valve
(m
3
/h)
4
4
6.3
PN valve
16
16
16
D
P max.
(kPa)
250
250
200
Connections
3/4”
3/4”
3/4”
All INNOV@DM-R CW units are supplied with 3-way valve setted by 3 points motor. Upon request, is possible to set an
advanced precision control with 0 ÷ 10 V signal regulation.
Air presence on hydraulic circuit
It is necessary to leak air from the hydraulic circuit of unit after the connection to the external circuit. To do this, open the
frontal panels and remove the air filter; after this ,open the small valve on the right-top side of the coil’s collector(take the
front side of unit in reference). Use adapted tools for the manual valve’s setting.