INNOV@ ECFAN DHR -AGU-0912-E
•
34
•
MODELS
DHZDR
DHZUR
1002
1204
Power supply
V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
21500
24000
WATER TEMPERATURE 15
C
/ 30
C
Cooling capacity
kW
107
138.5
Power consumption
kW
23.1
28
Waterflow
[l/h]
7180
9311
Pressure drop
[kPa]
18.4
13.5
COMPRESSOR
Type
-
Scroll
Power supply
V/Ph/Hz
400V / 3Ph / 50Hz
Nominal current
A
46.2
60.2
FLA
A
64
86
LRA
A
221
186
Oil charge
l
4.1
3.25
FINNED EVAPORATOR COIL
Front surface
m
2
2.3
2.9
Geometry
-
25 x 22
Rows
Nr.
6
6
Type of fins
Type
Hydrophilic
Fin pitch
mm
2.1
SHR
-
0.88
0.83
FAN SECTION
Type of fans
Tipo
Radial - EC
Fans
Nr.
2
3
Current consumption
A
6.6
4.9
Power consumption
W
3.9
2.9
AESP
Pa
30
AESP (max. fan speed)
Pa
226
440
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
5.2
5.2
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
14.8
14.8
Heaters
Nr.
5
5
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
-
-
Front surface
m
2
-
-
HOT WATER REHEATING COIL
Heating capacity (water 45/40
C)
kW
-
-
Front surface
m
2
-
-
Water flow
m
3
/h
-
-
Water side pressure drop
kPa
-
-
Valve pressure drop
kPa
-
-
HUMIDIFIER
Capacity
kg/h
8
Power consumption
kW
6
DIMENSIONS
Height x Lenght x Depth
mm
1998x2510x950
1998x3160x950
Unit weight
kg
1114
1529