INNOV@ ECFAN DHR -AGU-0912-E
•
32
•
tab. 12 DX unit (2 compressors) - water condensed - DHZDR - DHZUR
MODELS
DHZDR
DHZUR
0272
0302
0362
0422
0452
Power supply
V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
12950
WATER TEMPERATURE 15
C
/ 30
C
Cooling capacity
kW
27.90
34.60
40.60
48.00
50.60
Power consumption
kW
5.42
6.96
7.94
9.52
9.98
Waterflow
[l/h]
1957
2329
2768
3187
3369
Pressure drop
[kPa]
3
4.2
5.6
7.2
7.9
COMPRESSOR
Type
-
Scroll
Nominal current
V/Ph/Hz
400V / 3Ph / 50Hz
Nominal current
A
12.2
16.2
17.4
21.4
22.6
FLA
A
10
13
14
17
LRA
A
50
66
74
86
98
Oil charge
l
1.36
1.65
3.25
FINNED EVAPORATOR COIL
Front surface
m
2
1.3
Geometry
-
25 x 22
Rows
Nr.
3
4
Type of fins
Type
Hydrophilic
Fin pitch
mm
1.8
SHR
-
1.00
0.99
0.98
0.97
0.98
FAN SECTION
Type of fans
Tipo
Radial - EC
Fans
Nr.
2
Current consumption
A
4.3
4.4
Power consumption
W
2500
2595
2600
AESP
Pa
30
AESP (max. fan speed)
Pa
425
355
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
2.92
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
9.6
Heaters
Nr.
3
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
34.1
33.7
41.6
42.3
Front surface
m
2
1.05
HOT WATER REHEATING COIL
Heating capacity (water 45/40
C)
kW
39.6
41.0
42.0
Front surface
m
2
1.05
Water flow
m
3
/h
4.936
5.021
5.159
Water side pressure drop
kPa
39.6
41.0
42.0
Valve pressure drop
kPa
7.69
8.42
9.19
10.13
10.61
HUMIDIFIER
Capacity
kg/h
8
Power consumption
kW
6
DIMENSIONS
Height x Lenght x Depth
mm
1998 x 1750 x 795
Unit weight
kg
565
580
590
605
615