29
Smart Hub Parameters
Parameter
Description
Severe Weather Protection
(high and low temperature notification)
Options are enabled or disabled. Default is disabled. When enabled either the
heat or freezing alert temperature setting will automatically generate a email
notification to the homeowner that the applicable condition exist and homeowner
interaction is required.
Notification is dependent on the thermostat having a active Wi-Fi connection
and the user account has been setup and includes a valid email address.
Heat Alert Temperature
This will notified the homeowner when the indoor temperature reaches the
setting defined for this parameter. Range is 80°F to 100°F (26.67 to 37.78°C)
with a factory default of 90°F (32.22°C). Increments adjusted by 1.0°F (0.56°C).
Freezing Alert Temperature
This will notified the homeowner when the indoor temperature reaches the
setting defined for this parameter. Range is 30°F to 50°F (-1.11 to 10.0°C) with a
factory default of 40°F 4.4°C).
Increments adjusted by 1.0°F (0.56°C).
Smart Hub Parameters
Parameter
Description
Single Setpoint Mode (SSP)
On the user screens this is referred to as Perfect Temp (Temperature). Options
are enabled or disabled. Default is disabled. The Single Set Point (SSP)
algorithm allows the user the set only one temperature set point value rather
than one value for heating and a different value for cooling. When zoning
is present, the following SSP settings are not available. When enabled the
following parameters are automatically configured for optimal settings.
SSP Heating Cancel Coast Counter Increment Slope
Range is 0 to 0.75°F (0.0 to 0.42°C). Default is 0.25°F (-0.14°C). Adjustments
are in increments of 0.125°F (0.07°C).
SSP Heating Cancel Coast Counter Decrement Slope
Range is 0.25 to 2°F (0.14 to 1.11°C). Default is 0.5°F (0.28°C). Adjustments
are in increments of 0.125°F (0.07°C).
SSP Cooling Cancel Coast Counter Increment Slope
Range is -0.75 to 0.0°F (-0.42 to 0.0°C). Default is -0.25°F (-0.14°C).
Adjustments are in increments of 0.125°F (0.07°C).
SSP Cooling Cancel Coast Counter Decrement Slope
Range is -2.0 to -0.25°F (-1.11 to -0.14°C). Default is -0.5°F (-0.28°C).
Adjustments are in increments of 0.125°F (0.07°C).
SSP Heating Lockout Outdoor Temp
When the outdoor temperature is above this setting, heating is not allowed if
single set point is running. Range is 50 to 80°F (10.0 to 26.67°C). Default is
70°F (21.11°C). Adjustments are in increments of 1.0°F (0.56°C).
SSP Cooling Lockout Outdoor Temp
When the outdoor temperature is below this setting, cooling is not allowed if
single set point is running. Range is 30 to 60°F (-1.11 to 15.56°C). Default is
40°F (4.44°C). Adjustments are in increments of 1.0°F.