Ball Valve (Valve Open)

Schrader valve

service port

service port

cap

stem cap

stem

Use Adjustable Wrench

To open:  rotate Stem Counter-clockwise 90°.

To close:  rotate Stem Clockwise 90°.

ball

(shown open)

to outdoor coil

to indoor coil

Figure 12

Leak Testing

After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. 

WARNING

Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

 

WARNING

Danger of explosion:  Can cause
equipment damage, injury or death.
Never use oxygen to pressurize a re-
frigeration or air conditioning system.
Oxygen will explode on contact with
oil and could cause personal injury.

WARNING

Danger of explosion:  Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).

Using an Electronic Leak Detector

 1 − Connect a cylinder of R410A to the center port of the

manifold gauge set.

 2 − With both manifold valves closed, connect the cylinder

of R410A refrigerant. Open the valve on the R410A cyl-
inder (vapor only).

 3 − Open the high pressure side of the manifold to allow

R410A into the line set and indoor unit. Weigh in a trace
amount of R410A.

 [A trace amount is a maximum of 2

ounces (57 g) refrigerant or 3 pounds (31 kPa) pres-
sure]. 

Close the valve on the R410A cylinder and the

valve on the high pressure side of the manifold gauge
set. Disconnect R410A cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

 6 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open

the valve on the high side of the manifold gauge set in or-
der to pressurize the line set and the indoor unit.

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R410A
mixture. Correct any leaks and recheck.

IMPORTANT

Leak detector must be capable of sensing HFC re-
frigerant.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.

 1 − Connect manifold gauge set to the service valve ports

as follows:

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

Summary of Contents for HSXA12-018

Page 1: ...fied in Lennox Engineering Handbook Coils previously charged with R22 must be flushed INSTALLATION INSTRUCTIONS HSXA12 Series Units CONDENSING UNITS 504 540M 04 04 Supersedes 12 03 Table of Contents H...

Page 2: ...KIT 4 Field Installed 4 3 8 111 6 3 8 162 6 3 8 162 Top View Base Section 2 51 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL...

Page 3: ...the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either red wood or steel supports are recommended Electrical In the U S A wiri...

Page 4: ...Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is not equipped with blower relay It must be field...

Page 5: ...ft 50 ft 4 6 m 15 m 042 048 3 8 in 10 mm 7 8 in 22 mm 3 8 in 10 mm 7 8 in 22 mm L15 65 15 ft 50 ft 4 6 m 15 m 060 3 8 in 10 mm 1 1 8 in 29 mm 3 8 in 10 mm 1 1 8 in 29 mm Field Fabricated NOTE Units ar...

Page 6: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 7: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 8: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 7 Outsid...

Page 9: ...on device Do not leave the filter drier uncapped for more than 10 to 15 minutes prior to brazing evacuation and leak testing Polyol ester oils used in this system absorb mois ture quickly Failure to i...

Page 10: ...it Set the new R410A unit and follow the brazing connection procedure which begins on the previous page to make line set connections DO NOT install the provided fixed ori fice yet Make low voltage and...

Page 11: ...n instructions and the Lennox Engineering Handbook for approved TXV and fixed orifice match ups and application information Table 1 lists the unit liquid and vapor line sizes and corresponding line se...

Page 12: ...a 5 16 extension for vapor line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a se...

Page 13: ...ve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set Disconnect R410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center po...

Page 14: ...der of R410A refrigerant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R410A cylind...

Page 15: ...e the necessary load for properly charging the system in the cooling cycle 3 Use a digital thermometer to record the outdoor ambi ent temperature 4 When the heating demand has been satisfied switch th...

Page 16: ...144 565 9 52 147 4 83 246 5 114 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0...

Page 17: ...in the liquid state Some R410A cylinders are equipped with a dip tube which allows you to draw liquid refrigerant from the bottom of the cylin der without turning the cylinder upside down The cylinder...

Page 18: ...nnect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cooling season the system should be...

Page 19: ...n Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat Refri...

Reviews: