background image

Page 15

The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 feet (15.2 m). If oil must
be added to the compressor in the field, Copeland has
approved Mobil EAL

t

 Arctic 22CC and ICI EMKA-

RATE

t

 RL32CF.

Units Delivered Void of Charge

If the system is void of refrigerant,

 clean the system us-

ing the procedure described below.

 1 − Use nitrogen to pressurize the system and check for

leaks. Repair leaks, if possible.

 2 − Evacuate the system to remove as much of the mois-

ture as possible.

 3 − Use nitrogen to break the vacuum and install the pro-

vided filter drier in the system.

 4 − Evacuate the system again. Then, weigh the appropri-

ate amount of R410A refrigerant (listed on unit name-
plate) into the system.

 5 − Monitor the system to determine the amount of mois-

ture remaining in the oil. Use test kit 10N46 to verify
that the moisture content is within the kit’s dry color
range. It may be necessary to replace the filter drier
several times to achieve the required dryness level.

 If

system dryness is not verified, the compressor will
fail in the future.

Checking Charge

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is deter-

mined by the unit’s 

refrigerant metering device

 and the

outdoor ambient temperature

.

Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:

 1 − Connect the manifold gauge set to the service valves:

 

 

low pressure gauge to 

vapor 

valve service port

 

 

high pressure gauge to 

liquid 

valve service port

Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of R410A .

 2 − Set the room thermostat to call for heat. This will create

the necessary load for properly charging the system in
the cooling cycle.

 3 − Use a digital thermometer to record the outdoor ambi-

ent temperature.

 4 − When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68

F

(20

C). When pressures have stabilized, use a digital

thermometer to record the liquid line temperature.

 5 − The outdoor temperature will determine which charg-

ing method to use. Proceed with the appropriate charg-
ing procedure.

Weighing in the Charge Fixed Orifice

 

or

TXV Systems – Outdoor Temp. < 65

F (18

C)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been re-
paired.

 1 − Recover the refrigerant from the unit.

 2 − Conduct a leak check, then evacuate as previously

outlined.

 3 − Weigh in the unit nameplate charge.

If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce-
dures outlined below.

Charging Using the Subcooling

 

Method

Fixed Orifice Systems

Outdoor Temp. > 65

F (18

C))

If you charge a fixed orifice system when the outdoor ambi-
ent is 65

F (18

C) or above, use the subcooling method to

charge the unit.

 1 − With the manifold gauge hose still on the liquid service

port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.

 2 − At the same time, record the liquid line pressure reading.

 3 − Use a temperature/pressure chart for R410A to deter-

mine the saturation temperature for the liquid line pres-
sure reading. See table 5.

 4 − Subtract the liquid line temperature from the saturation

temperature (according to the chart) to determine sub-
cooling. 

(Saturation temperature − Liquid line tem-

perature = Subcooling)

 5 − Compare the subcooling value with those in table 6. If

subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant.

Summary of Contents for HSXA12-018

Page 1: ...fied in Lennox Engineering Handbook Coils previously charged with R22 must be flushed INSTALLATION INSTRUCTIONS HSXA12 Series Units CONDENSING UNITS 504 540M 04 04 Supersedes 12 03 Table of Contents H...

Page 2: ...KIT 4 Field Installed 4 3 8 111 6 3 8 162 6 3 8 162 Top View Base Section 2 51 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL...

Page 3: ...the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either red wood or steel supports are recommended Electrical In the U S A wiri...

Page 4: ...Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is not equipped with blower relay It must be field...

Page 5: ...ft 50 ft 4 6 m 15 m 042 048 3 8 in 10 mm 7 8 in 22 mm 3 8 in 10 mm 7 8 in 22 mm L15 65 15 ft 50 ft 4 6 m 15 m 060 3 8 in 10 mm 1 1 8 in 29 mm 3 8 in 10 mm 1 1 8 in 29 mm Field Fabricated NOTE Units ar...

Page 6: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 7: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 8: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 7 Outsid...

Page 9: ...on device Do not leave the filter drier uncapped for more than 10 to 15 minutes prior to brazing evacuation and leak testing Polyol ester oils used in this system absorb mois ture quickly Failure to i...

Page 10: ...it Set the new R410A unit and follow the brazing connection procedure which begins on the previous page to make line set connections DO NOT install the provided fixed ori fice yet Make low voltage and...

Page 11: ...n instructions and the Lennox Engineering Handbook for approved TXV and fixed orifice match ups and application information Table 1 lists the unit liquid and vapor line sizes and corresponding line se...

Page 12: ...a 5 16 extension for vapor line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a se...

Page 13: ...ve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set Disconnect R410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center po...

Page 14: ...der of R410A refrigerant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R410A cylind...

Page 15: ...e the necessary load for properly charging the system in the cooling cycle 3 Use a digital thermometer to record the outdoor ambi ent temperature 4 When the heating demand has been satisfied switch th...

Page 16: ...144 565 9 52 147 4 83 246 5 114 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0...

Page 17: ...in the liquid state Some R410A cylinders are equipped with a dip tube which allows you to draw liquid refrigerant from the bottom of the cylin der without turning the cylinder upside down The cylinder...

Page 18: ...nnect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cooling season the system should be...

Page 19: ...n Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat Refri...

Reviews: