Page 17
Approach Method and
Normal Operating Pressures
TXV Systems – Outdoor Temp. > 65
F (18
C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 8, Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid
line temperature.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 7. If the val-
ues don’t agree with the those in table 7, add refriger-
ant to lower the approach temperature, or recover re-
frigerant from the system to increase the approach
temperature.
Be aware of the R410A refrigerant cylinder. It will be
rose−colored. Refrigerant should be added through the
vapor valve in the liquid state.
Some R410A cylinders
are equipped with a dip tube which allows you to
draw liquid refrigerant from the bottom of the cylin-
der without turning the cylinder upside−down. The
cylinder will be marked if it is equipped with a dip
tube.
Table 7
HSXA12 Approach Values
Model No.
Approach Temperature
Liquid Line −
Outdoor Ambient °F (°C)
−018
10 (5.6)
−024
12 (6.7)
−030
13 (7.2)
−036
12 (6.7)
−042
11 (6.1)
−048
13 (7.2)
−060
14 (7.8)
IMPORTANT
Use table 8 to perform maintenance checks. Table 8
is not a procedure for charging the system. Minor
variations in these pressures may be due to differ-
ences in installations. Significant deviations could
mean that the system is not properly charged or that
a problem exists with some component in the system.
Table 8
Normal Operating Pressures In psig (/− 10 and vapor +/− 5 PSIG)*
Mode
Out. Coil
Entering Air
Temp
−018
−024
−030
−036
−042
−048
−060
Mode
Temp.
°
F (
°
C)
LIQ
SUC
LIQ
SUC
LIQ
SUC
LIQ
SUC
LIQ
SUC
LIQ
SUC
LIQ
SUC
65 (18.3)
238
123
261
131
261
128
268
130
254
121
270
124
280
121
75 (23.9)
275
131
300
135
300
133
308
134
296
128
311
130
332
126
fixed
ifi
85 (29.4)
317
136
343
139
343
138
351
138
340
133
356
134
379
130
orifice
95 (35.0)
362
141
391
143
387
141
398
142
389
138
404
139
427
135
105 (40.6)
410
144
441
147
434
145
447
146
440
142
456
143
479
140
65 (18.3)
234
133
256
134
256
137
264
135
256
124
269
131
262
121
75 (23.9)
270
135
298
137
296
139
305
138
296
127
312
133
304
127
TXV
85 (29.4)
312
137
344
140
339
141
349
139
341
133
357
135
349
132
95 (35.0)
361
138
394
142
384
144
396
140
389
136
406
137
397
136
105 (40.6)
409
141
448
143
432
146
446
143
440
140
460
140
449
140
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures
to vary.