background image

Page 16

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches  of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves to
break the vacuum in the line set and indoor unit. Close
the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise
above 500 microns (29.9 inches of mercury) within a
20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.

C − Charging

WARNING

Refrigerant can be harmful if inhaled. Refrigerant
must be used and recovered responsibly. Failure
to follow this warning can lead to injury or death.

Units are factory charged with the amount of R410A refrig-
erant indicated on the unit rating plate. This charge is based
on a matching indoor coil and outdoor coil with 15 ft. (4.5m)
line set. See table 4 for varying lengths of line set and
charge adjustment. The check/expansion valve provided
with the unit is approved for use with R410A. Do not replace
it with a valve designed for use with R22. This unit is NOT
approved for use with coils which include metering orifices
or capillary tubes.

TABLE 4

Liquid Line Set

Diameter

Oz. per 5 ft. (grams per 1.5 m) adjust 

from 15 ft. (4.5 m) line set*

3/8 in.

(10 mm)

3 ounces per 5 feet

(85g per 1.5 m)

*If line length is greater than 15 ft. (4.5 m), add this amount.
If line length is less than 15 ft. (4.5 m), subtract this amount.

Units are designed for line sets up to 50 feet (15.2 m). Con-
sult Lennox Refrigeration Piping Manual for line sets over
50 feet (15.2 m).

IMPORTANT

Mineral oils are not compatible with R410A. If oil
must be added, it must be a polyol ester oil.

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is determined

by the unit’s 

refrigerant metering device

 and the 

outdoor

ambient temperature

.

Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:

 1 − Connect the manifold gauge set to the service valves:

 

 

low pressure gauge to 

vapor 

valve service port

 

 

high pressure gauge to 

liquid 

valve service port

Connect the center manifold hose to an upright cylinder
of R410A. Close manifold gauge set valves.

 2 − Set the room thermostat to call for heat. This will create

the necessary load for properly charging the system in
the cooling cycle.

 3 − Use a digital thermometer to record the outdoor ambi-

ent temperature.

 4 − When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68

F

(20

C). When pressures have stabilized, use a digital

thermometer to record the liquid line temperature.

 5 − The outdoor temperature will determine which charg-

ing method to use. Proceed with the appropriate charg-
ing procedure.

Summary of Contents for HPXA12 SERIES

Page 1: ...quipment rated for R410A WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning o...

Page 2: ...80 181 82 OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Monitor Canada Only 45F08 45F08 45F08 45F08 Hail Guards 17L73 17L73 17L73 17L73 Mild Ambient Kit LB 101122 32M08 32M08 32M08 32M08 Monit...

Page 3: ...B2 L 69J07 Mounting Base Net Weight 6 lbs 3 kg 15 lbs 7 kg 15 lbs 7 kg Refrigerant Li S t 30 ft 9 m length L15 65 30 L15 65 30 Field Fabricate g Line Set 40 ft 12 m length L15 65 40 L15 65 40 Field Fa...

Page 4: ...62 Power Factor 98 98 99 99 99 99 Outdoor Coil F M t Full load amps 1 55 1 9 9 1 9 9 Fan Motor Locked Rotor Amps 2 3 1 4 1 2 1 4 1 2 1 OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Low Ambient...

Page 5: ...early compressor failure IMPORTANT This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook II UNIT COMPONENTS Unit components are illustrated in figure 1 COMPRESSOR C...

Page 6: ...nal Y2 for 2nd stage thermostat input 46M8201 56M8501 DELAY pins 56M8501 The demand defrost board uses basic differential temper ature means to detect degradation of system performance due to ice buil...

Page 7: ...e Y1 Out line is engaged a 5 minute short cycle will occur after the switch closes Operational Description The demand defrost board has three basic operational modes Normal Defrost and Calibration Nor...

Page 8: ...period If the board fails to calibrate another defrost cycle will be initiated after 90 minutes of heating mode compressor run time Once the defrost board is calibrated it will use de mand defrost log...

Page 9: ...e board and all sensors FLASH FLASH Normal operation Unit operating normally or in standby mode None required ON OFF Strike Out pressure lockout Short test pins or reset 24V power to board to override...

Page 10: ...the two scrolls figure 10 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 10 2 As the orbiting motion contin ues the gas is forced toward the center of the s...

Page 11: ...uire a run capacitor In all units the condenser fan is controlled by the compressor contactor ELECTRICAL DATA tables in this manual show specifi cations for condenser fans used in HPXA12s Access to th...

Page 12: ...ch settings for R410A refrigerant will be significantly higher than units with R22 An auto reset single pole single throw high pressure switch is located in the liquid line This switch shuts off the c...

Page 13: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 14: ...em out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap Tighten finger tight then tighten an...

Page 15: ...e high pres sure hose is connected to the liquid line port however connecting it to the vapor port better protects the man ifold gauge set from high pressure damage 6 Adjust the nitrogen pressure to 1...

Page 16: ...injury or death Units are factory charged with the amount of R410A refrig erant indicated on the unit rating plate This charge is based on a matching indoor coil and outdoor coil with 15 ft 4 5m line...

Page 17: ...for checking charge Block equal sections of air intake panels mov ing obstructions sideways as shown until liquid pres sure is in the 300 350 psig 2068 2413 kPa range BLOCKING OUTDOOR COIL CARDBOARD O...

Page 18: ...344 127 380 128 335 100 TABLE 8 R410A Temperature Pressure Chart Temperature F Pressure Psig Temperature F Pressure Psig Temperature F Pressure Psig Temperature F Pressure Psig 32 100 8 63 178 5 94 29...

Page 19: ...eplaced to eliminate moisture from POE oil VI MAINTENANCE In order to maintain the warranty on this equipment the HPXA12 system must be serviced annually and a record of service maintained The followi...

Page 20: ...Page 20 VII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 7 8 9 10 11 12 13 15 1 2 3 4 14 1 4 HPXA12 1 5 THROUGH 5 TON UNIT WIRING Single Phase 230V...

Page 21: ...Page 21 5 6 7 8 9 10 11 12 13 15 2 3 14 1 4 HPXA12 3 THROUGH 5 TON UNIT WIRING Three Phase 230V 7...

Page 22: ...Page 22 5 6 7 8 9 10 11 12 13 15 2 3 14 1 4 HPXA12 3 THROUGH 5 TON UNIT WIRING Three Phase 460V 7...

Page 23: ...K1 5 minute anti cylce time must be satisfied first 11 K1 1 N O closes energizing compressor and out door fan motor 460V units only K1 1 closes energizing compressor B1 and outdoor relay K10 energizin...

Reviews: