background image

Page 8

IMPORTANT

Service valves are closed to the heat pump unit and
open to line set connections. Do not open until re-
frigerant lines have been leak tested and evacuat-
ed. All precautions should be exercised in keeping
the system free from dirt, moisture and air.

Accessing the Schrader Port:

1 − Remove service port cap with an adjustable wrench.

2 − Connect gauge to the service port.

3 − When  testing  is  completed,  replace  the  service  port

cap. Tighten finger tight, then tighten an additional 1/6
turn.

To Open Liquid or Vapor Line Service Valve:

1 − Remove the stem cap with an adjustable wrench.

2 − Use a service wrench with a hex−head extension to

back the stem out counterclockwise as far as pos-
sible.

WARNING

Do not attempt to backseat this valve. Attempts to
backseat this valve will cause the snap ring to ex-
plode from the valve body under pressure of the re-
frigerant. Personal injury and unit damage will result.

3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

To Close Liquid or Vapor Line Service Valve:

1 − Remove the stem cap with an adjustable wrench.

2 − Use a service wrench with a hex−head extension to

turn the stem clockwise to seat the valve. Tighten
firmly.

3 − Replace the stem cap. Tighten finger tight, then tight-

en an additional 1/6 turn.

VAPOR LINE (BALL−TYPE) SERVICE VALVE

(VALVE OPEN)

SCHRADER

VALVE

SERVICE PORT

SERVICE

PORT

CAP

STEM CAP

TO OUTDOOR

COIL

STEM

USE ADJUSTABLE WRENCH.

ROTATE STEM CLOCKWISE 90

 TO CLOSE.

ROTATE STEM COUNTERCLOCKWISE 90

 TO OPEN.

BALL

(SHOWN OPEN)

TO INDOOR COIL

FIGURE 8

Vapor Line (Ball−Type) Service Valve −− 5−Ton Units

A ball-type full−service valve is  used on five-ton units. These
vapor line service valves function the same way, the differ-
ences are in construction. Valves are not rebuildable. If a
valve has failed, it must be replaced. A ball valve is il-
lustrated in figure 8.
The ball valve is equipped with a service port and a  fac-
tory−installed Schrader valve. A service port cap is
supplied to protect the Schrader valve from contami-
nation and to assure a leak−free seal.

Leak Testing

After the line set has been connected to the indoor and
outdoor units, check all connections for leaks.

IMPORTANT

The leak detector must be capable of sensing HFC
refrigerant.

WARNING

Never use oxygen to pressurize refrigeration or air
conditioning system. Oxygen will explode on con-
tact with oil and could cause personal injury. When
using high pressure gas such as nitrogen for this
purpose, be sure to use a regulator that can control
the pressure down to a range of 6.9 to 13.8 kPa.

Using an Electronic Leak Detector

1 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to center port of manifold gauge set.

2 − Connect the high pressure hose of the manifold

gauge set to the service port of the vapor valve. (Nor-
mally, the high pressure hose is connected to the liq-
uid line port, however, connecting it to the vapor port
better protects the manifold gauge set from high pres-
sure damage.)

3 − With both manifold valves closed, open the valve on

the R407C cylinder (liquid only).

4 − Open the high pressure side of the manifold to allow

R407C into the line set and indoor unit. Weigh in a
trace amount of R407C. (A trace amount is a maxi-
mum of 59 ml or 21 kPa pressure.)

 

Close the valve on

the R407C cylinder and the valve on the high pres-
sure side of the manifold gauge set. Disconnect
R407C cylinder and attach a nitrogen cylinder.

5 − Adjust nitrogen pressure to 1034 kPa. Open the valve

on the high side of the manifold gauge set which will
pressurize line set and indoor unit.

6 − After a short period of time, open a refrigerant port to

make sure the refrigerant added is adequate to be de-
tected. (Amounts of refrigerant will vary with line
lengths.) Check all joints for leaks. Purge nitrogen
and R407C mixture. Correct any leaks and recheck.

Summary of Contents for HP40

Page 1: ...th INSTALLATION INSTRUCTIONS HP40 Heat Pump Units HEAT PUMP UNITS 1 1 2 through 5 ton 504 538M 06 04 Supersedes 11 02 Table of Contents HP40 Heat Pump Unit 1 Shipping Packing List 1 General Informatio...

Page 2: ...ICAL INLETS 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL STAND OFF KIT Field installed 4 required LIQUID LINE CONNECTION...

Page 3: ...a support frame is constructed it must not block drain holes in the base of the unit 4 When you install the unit in areas where low ambient temperatures exist locate the unit so winter prevail ing win...

Page 4: ...sunlight drafts or vibration Do not install the thermostat on an outside wall The most desirable position for the thermostat is near the cen ter of the conditioned area and approximately 1 5 m from t...

Page 5: ...it is being matched with an approved line set or indoor coil which was previously charged with R22 refrigerant or if it is being matched with a coil which was manufactured before January of 1999 the c...

Page 6: ...The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushing cylinder before proceeding 5 Set th...

Page 7: ...e sets used with systems charged with R407C refrigerant must be able to accommodate higher system operating pressures The gauges should be rated for pressures of 0 800 psi on the high side and a low s...

Page 8: ...ced A ball valve is il lustrated in figure 8 The ball valve is equipped with a service port anda fac tory installed Schrader valve A service port cap is supplied to protect the Schrader valve from con...

Page 9: ...0 microns of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from the vacuum pump Attach the manifold center port hose to a nitro ge...

Page 10: ...C airflow over the outdoor coil will need to be reduced to drive up the liquid line pressure to a range of 1379 to 1724 kPa To do this block off the outdoor coil with cardboard or a plas tic sheet BLO...

Page 11: ...2 21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 1...

Page 12: ...o allow the crankcase heater sufficient time to prevent compressor from slugging Defrost System The HP40 defrost system includes two components a de frost thermostat and a defrost control Defrost Ther...

Page 13: ...using a pressure switch the factory installed jumper wire must be connected Diagnostic LEDs The defrost board uses two LEDs for diagnostics The LEDs flash a specific sequence according to the conditi...

Page 14: ...Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off Outdoor Coil Entering Air Temperature Discharge Pressur...

Page 15: ...Page 15...

Page 16: ...Page 16 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: