background image

Page 9

System Evacuation

WARNING

Unit contains a NITROGEN holding charge. The
holding charge must be purged and the system
must be evacuated prior to charging with R407C.

Evacuating the system of non−condensables is critical for
the unit to operate properly. Non−condensables are de-
fined as any gas that will not condense under temperatures
and pressures present during operation of an air condition-
ing system. Non−condensables and water vapor combine
with refrigerant to produce substances that corrode copper
piping and compressor parts.

 1− Connect manifold gauge set to the service valve ports

as follows:
 

 

low pressure gauge to 

suction 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

IMPORTANT − Compliant scroll compressors (as with
any refrigerant compressor) should never be used to
evacuate a refrigeration or air conditioning system.

NOTE − Use a temperature vacuum gauge, mercury
vacuum, or thermocouple gauge. The usual Bourdon
tube gauges are inaccurate in the vacuum range.

  2 −The nitrogen holding charge in the unit must be re-

leased. Open both manifold valves to release the ni-
trogen from the unit. See the liquid and suction line
service valves section for how to operate the service
valves.

  3 −Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

  4 −Open  both  manifold  valves  and  start  the  vacuum

pump.

  5 −Evacuate the line set, condensing unit, and indoor

unit to an 

absolute pressure

 of 23 mm (23,000 mi-

crons) of mercury. During the early stages of evacua-
tion, it is desirable to close the manifold gauge valve
at least once to determine if there is a rapid rise in 

ab-

solute pressure

. A rapid rise in pressure indicates a

relatively large leak. If this occurs, the leak testing
procedure must be repeated.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure
minus vacuum pressure.

  6 −When the absolute pressure reaches 23 mm (23,000

microns) of mercury, close the manifold gauge
valves, turn off the vacuum pump, and disconnect the
manifold gauge center port hose from the vacuum
pump. Attach the manifold center port hose to a nitro-

gen cylinder with the pressure regulator set to 150
psig (1034 kPa) and purge the hose. Open the man-
ifold gauge valves to break the vacuum in the system.
Close the manifold gauge valves.

WARNING

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use com-
pressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.

  7 −Shut off the nitrogen cylinder and remove the man-

ifold gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the system.

  8 −Reconnect the manifold gauge to the vacuum pump,

turn the pump on and continue to evacuate the system
until the absolute pressure does not rise above .5 mm
(500 microns) of mercury within a 20−minute period af-
ter shutting off the vacuum pump and closing the man-
ifold gauge valves.

 9 − When the absolute pressure requirement from step 9

has been met, disconnect the manifold gauge hose
from the vacuum pump. Then, weigh in a LIQUID
charge of R407C through the liquid and suction ser-
vice valves.

Refer to the unit nameplate for the correct liquid
charge. If you can not measure in the total amount, re-
fer to the start−up section and set the final system
charge according to the charging instructions. 

The

R407C refrigerant cylinder should be chocolate
brown.

Start−Up

Cooling Start-Up

1 − Check the unit disconnect switch to make sure power

is off.

2 − Rotate the fan to check for frozen bearings or binding.

3 − Inspect all factory and field-installed wiring for loose

connections.

4 − Replace the stem caps. Tighten finger tight, then

tighten an additional 1/6 turn.

5 − Check the voltage supply at the disconnect switch.

The voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
you have consulted the power company, and the volt-
age condition has been corrected.

6 − Set the thermostat for cooling demand, turn on the

power to the indoor blower coil, and close the heat
pump unit disconnect switch to start the unit.

Summary of Contents for HP40

Page 1: ...th INSTALLATION INSTRUCTIONS HP40 Heat Pump Units HEAT PUMP UNITS 1 1 2 through 5 ton 504 538M 06 04 Supersedes 11 02 Table of Contents HP40 Heat Pump Unit 1 Shipping Packing List 1 General Informatio...

Page 2: ...ICAL INLETS 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL STAND OFF KIT Field installed 4 required LIQUID LINE CONNECTION...

Page 3: ...a support frame is constructed it must not block drain holes in the base of the unit 4 When you install the unit in areas where low ambient temperatures exist locate the unit so winter prevail ing win...

Page 4: ...sunlight drafts or vibration Do not install the thermostat on an outside wall The most desirable position for the thermostat is near the cen ter of the conditioned area and approximately 1 5 m from t...

Page 5: ...it is being matched with an approved line set or indoor coil which was previously charged with R22 refrigerant or if it is being matched with a coil which was manufactured before January of 1999 the c...

Page 6: ...The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushing cylinder before proceeding 5 Set th...

Page 7: ...e sets used with systems charged with R407C refrigerant must be able to accommodate higher system operating pressures The gauges should be rated for pressures of 0 800 psi on the high side and a low s...

Page 8: ...ced A ball valve is il lustrated in figure 8 The ball valve is equipped with a service port anda fac tory installed Schrader valve A service port cap is supplied to protect the Schrader valve from con...

Page 9: ...0 microns of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from the vacuum pump Attach the manifold center port hose to a nitro ge...

Page 10: ...C airflow over the outdoor coil will need to be reduced to drive up the liquid line pressure to a range of 1379 to 1724 kPa To do this block off the outdoor coil with cardboard or a plas tic sheet BLO...

Page 11: ...2 21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 1...

Page 12: ...o allow the crankcase heater sufficient time to prevent compressor from slugging Defrost System The HP40 defrost system includes two components a de frost thermostat and a defrost control Defrost Ther...

Page 13: ...using a pressure switch the factory installed jumper wire must be connected Diagnostic LEDs The defrost board uses two LEDs for diagnostics The LEDs flash a specific sequence according to the conditi...

Page 14: ...Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off Outdoor Coil Entering Air Temperature Discharge Pressur...

Page 15: ...Page 15...

Page 16: ...Page 16 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: