background image

Page 6

the low pressure switches to ensure complete refrig-
erant evacuation.) When low side system pressures
reach 0 psig, close the suction line valve. Disconnect
all power to the existing outdoor unit. Refer to gauges
after shutdown to confirm that the valves are not al-
lowing refrigerant to flow back into the low side of the
system. Disconnect the liquid and vapor lines from
the existing outdoor unit.

 2 − Remove the existing outdoor unit. Set the new

R407C unit and follow the brazing connection proce-
dure to make line set connections. 

DO NOT install

provided R407C check/expansion valve at this
time.

Make low voltage and line voltage connections to the
new outdoor unit. 

DO NOT turn on power to the

unit or open the outdoor unit service valves at
this time.

 3 − Remove the existing refrigerant flow control orifice or

thermal expansion/check valve before continuing
with flushing procedures.  The existing devices are
not approved for use with R407C refrigerant and may
prevent proper flushing. Use a field−provided fitting to
reconnect the lines.

 4 − Remove the pressure tap valve cores from the HP32

unit’s service valves. Connect an R22 cylinder with
clean refrigerant to the suction service valve. Con-
nect the R22 gauge set to the liquid line valve and
connect a recovery machine with an empty recovery
tank to the gauge set.

IMPORTANT

The line set and indoor coil must be flushed with
at least the same amount of clean refrigerant that
previously charged the system. Check the charge
in the flushing cylinder before proceeding.

 5 − Set the recovery machine for liquid recovery and

start the recovery machine. Open the gauge set
valves to allow the recovery machine to pull a vacu-
um on the existing system line set and indoor coil.

 6 − Invert the cylinder of clean R22 and open its valve to

allow liquid refrigerant to flow into the system through
the suction line valve. Allow the refrigerant to pass
from the cylinder, through the line set and the indoor
coil before entering the recovery machine.

 7 − After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so
that all of the R22 vapor is recovered. All the recovery
machine to pull a vacuum on the system.

NOTE − A single system flush should remove all of
the mineral oil from the existing refrigerant lines and
indoor coil. A second flushing may be done (using
clean refrigerant) if insufficient amounts of mineral oil
were removed during the first flush.

 Each time the

system is flushed, you must allow the recovery
machine to pull a vacuum on the system at the
end of the procedure.

FLUSHING CONNECTIONS

LOW

PRESSURE

HIGH

PRESSURE

SUCTION LINE

SERVICE VALVE

INDOOR COIL

HP40 UNIT

GAUGE MANIFOLD

RECOVERY MACHINE

INVERTED R22

CYLINDER

LIQUID LINE

SERVICE VALVE

INLET

DISCHARGE

TANK RETURN

CLOSED

OPENED

EXISTING

EXISTING SUCTION LINE

EXISTING LIQUID LINE

RECOVERY

CYLINDER

FIGURE 5

Summary of Contents for HP40

Page 1: ...th INSTALLATION INSTRUCTIONS HP40 Heat Pump Units HEAT PUMP UNITS 1 1 2 through 5 ton 504 538M 06 04 Supersedes 11 02 Table of Contents HP40 Heat Pump Unit 1 Shipping Packing List 1 General Informatio...

Page 2: ...ICAL INLETS 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL STAND OFF KIT Field installed 4 required LIQUID LINE CONNECTION...

Page 3: ...a support frame is constructed it must not block drain holes in the base of the unit 4 When you install the unit in areas where low ambient temperatures exist locate the unit so winter prevail ing win...

Page 4: ...sunlight drafts or vibration Do not install the thermostat on an outside wall The most desirable position for the thermostat is near the cen ter of the conditioned area and approximately 1 5 m from t...

Page 5: ...it is being matched with an approved line set or indoor coil which was previously charged with R22 refrigerant or if it is being matched with a coil which was manufactured before January of 1999 the c...

Page 6: ...The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushing cylinder before proceeding 5 Set th...

Page 7: ...e sets used with systems charged with R407C refrigerant must be able to accommodate higher system operating pressures The gauges should be rated for pressures of 0 800 psi on the high side and a low s...

Page 8: ...ced A ball valve is il lustrated in figure 8 The ball valve is equipped with a service port anda fac tory installed Schrader valve A service port cap is supplied to protect the Schrader valve from con...

Page 9: ...0 microns of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from the vacuum pump Attach the manifold center port hose to a nitro ge...

Page 10: ...C airflow over the outdoor coil will need to be reduced to drive up the liquid line pressure to a range of 1379 to 1724 kPa To do this block off the outdoor coil with cardboard or a plas tic sheet BLO...

Page 11: ...2 21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 1...

Page 12: ...o allow the crankcase heater sufficient time to prevent compressor from slugging Defrost System The HP40 defrost system includes two components a de frost thermostat and a defrost control Defrost Ther...

Page 13: ...using a pressure switch the factory installed jumper wire must be connected Diagnostic LEDs The defrost board uses two LEDs for diagnostics The LEDs flash a specific sequence according to the conditi...

Page 14: ...Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off Outdoor Coil Entering Air Temperature Discharge Pressur...

Page 15: ...Page 15...

Page 16: ...Page 16 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: