background image

3DJH 

SETTING THE UNIT

Heat pump units operate under a wide range of
weather conditions; therefore, several factors must
be considered when positioning the outdoor unit.
Unit must be positioned to give adequate clearances
for sufficient airflow and servicing. A minimum clear-
ance of 36 in. (914 mm) between multiple units must
be maintained. Refer to figure 1 for installation clear-
ances.

INSTALLATION CLEARANCES

FIGURE 1

36

(914 mm)

*36

(914 mm)

36

(914 mm)

NOTE—48 inch clearance required on top of unit.

*36

(914 mm)

*NOTE—One side must be 36 inches. Two of the remaining

three sides may be 12 inches.

1- Place a sound-absorbing material, such as Iso-

mode, under the unit if it will be installed in a loca-
tion or position that will transmit sound or vibra-
tion to the living area or adjacent buildings.

2- Mount unit high enough above ground or roof to

allow adequate drainage of defrost water and
prevent ice build-up.

3- In heavy snow areas, do not locate unit where

drifting will occur. The unit base should be ele-
vated above the depth of average snows.
NOTE-Elevation of the unit may be accomplished
by constructing a frame using suitable materials.
If a support frame is constructed, it must not block
drain holes in unit base.

4- When installed in areas where low ambient tem-

peratures exist, locate unit so winter prevailing
winds do not blow directly into outdoor coil.

5- Locate unit away from overhanging roof lines

which would allow water or ice to drop on, or in
front of, coil or into unit.

Slab Mounting--Figure 2

When installing unit at grade level, top of slab should
be high enough above the grade so that water from
higher ground will not collect around unit. See figure
2. Slab should have a slope tolerance away from the
building of 2 degrees or 2 inches per 5 feet (51 mm per
1524 mm). This will prevent ice build-up under the
unit during a defrost cycle. Refer to roof mounting
section for barrier construction if unit must face pre-
vailing winter winds.

FIGURE 2

SLAB MOUNTING AT GROUND LEVEL

DISCHARGE AIR

MOUNTING SLAB MUST SLOPE

AWAY FROM BUILDING.

GROUND LEVEL

STRUCTURE

Roof Mounting--Figure 3

Install unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build--up around the unit. Lo-
cate the unit above a load bearing wall or area of the
roof that can adequately support the unit. Consult lo-
cal codes for rooftop applications.

FIGURE 3

WIND BARRIER

INLET AIR

INLET AIR

INLET AIR

INLET AIR

PREVAILING WINTER WINDS

ROOFTOP APPLICATION

WIND BARRIER CONSTRUCTION

Summary of Contents for HP23-141

Page 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Page 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Page 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Page 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Page 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Page 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Page 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Page 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Page 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Page 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Page 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Page 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Reviews: