background image

3DJH 

(9$&8$7,1*

Evacuating the system of non--condensables is criti-

cal for proper operation of the unit. Non--condens-

ables are defined as any gas that will not condense

under temperatures and pressures present during

operation of an air conditioning system. Non--con-

densables such as water vapor, combine with refrig-

erant to produce substances that corrode copper pip-

ing and compressor parts.

  &RQQHFW PDQLIROG JDXJH VHW WR WKH VHUYLFH YDOYH

SRUWV DV IROORZV ORZ SUHVVXUH JDXJH WR YDSRU OLQH
VHUYLFH YDOYH KLJK SUHVVXUH JDXJH WR OLTXLG OLQH VHU
YLFH YDOYH

2-- Connect the vacuum pump (with vacuum gauge)

to the center port of the manifold gauge set.

3-- Open both manifold valves and start vacuum

pump.

4-- Evacuate the line set and indoor unit to an abso-

lute pressure of 23mm of mercury or approxi-

mately 1 inch of mercury. During the early stages

of evacuation, it is desirable to close the manifold

gauge valve at least once to determine if there is a

rapid rise in absolute pressure. A rapid rise in

pressure indicates a relatively large leak. If this oc-

curs, the leak testing procedure must be repeated.
NOTE -- The term absolute pressure means the to-
tal actual pressure within a given volume or sys-
tem, above the absolute zero of pressure. Abso-
lute pressure in a vacuum is equal to atmospheric
pressure minus vacuum pressure.

5-- When the absolute pressure reaches 23mm of

mercury, close the manifold gauge valves, turn

off the vacuum pump and disconnect the man-

ifold gauge center port hose from vacuum pump.

Attach the manifold center port hose to a nitrogen

cylinder with pressure regulator set to 150 psig

and purge the hose. Open the manifold gauge

valves to break the vacuum in the line set and in-

door unit. Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.

Avoid deep vacuum operation. Do not use com-

pressors to evacuate a system.

Extremely low vacuums can cause internal arc-

ing and compressor failure.

Damage caused by deep vacuum operation will

void warranty.

6-- Shut off the nitrogen cylinder and remove the

manifold gauge hose from the cylinder. Open the

manifold gauge valves to release the nitrogen

from the line set and indoor unit.

7-- Reconnect the manifold gauge to the vacuum

pump, turn the pump on and continue to evacuate

the line set and indoor unit until the absolute pres-

sure does not rise above 5mm of mercury within a

20 minute period after shutting off the vacuum

pump and closing the manifold gauge valves.

8-- Depending on the equipment used to determine

the vacuum level, the following units are equiva-

lent to absolute pressure of 5mm of mercury:

5000 microns; 754 millimeters of mercury vacu-

um pressure; or 29.7 inches of mercury vacuum

pressure.

9-- When the absolute pressure requirement above

has been met, disconnect the manifold hose from

the vacuum pump and connect it to an upright

bottle of R22 refrigerant. Open the manifold gauge

valves to break the vacuum in the line set and in-

door unit. Close manifold gauge valves and shut

off R22 bottle and remove manifold gauge set.

67$5783

IMPORTANT

Crankcase heater should be energized 24 hours

before unit start--up to prevent compressor dam-

age as a result of slugging.

1- Rotate fan to check for frozen bearings or binding.
2- Inspect all factory and field-installed wiring for

loose connections.

3- Open liquid line and vapor line service valves

(counterclockwise) to release refrigerant charge

(contained in heat pump unit) into the system.

4- Replace stem caps and secure finger tight, then

tighten an additional (1/6) one--sixth of a turn.

5- Check voltage supply at the disconnect switch.

The voltage must be within the range listed on the

unit nameplate. If not, do not start the equipment

until the power company has been consulted and

the voltage condition has been corrected.

6- Set the thermostat for a cooling demand, turn on

power to indoor blower coil and close heat pump

unit disconnect to start unit.

7- Recheck unit voltage with unit running. Power

must be within range shown on unit nameplate.

Check amperage draw of unit. Refer to unit name-

plate for correct running amps.

&+$5*,1* &216,'(5$7,216

The unit is factory charged with the amount of R-22

refrigerant indicated on the unit rating plate. This

charge is based on a matching indoor coil and out-

door coil with a 20 foot (6096 mm) line set. For vary-

ing lengths of line set, refer to table 2 for refrigerant

charge adjustment.

Summary of Contents for HP23-141

Page 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Page 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Page 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Page 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Page 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Page 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Page 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Page 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Page 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Page 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Page 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Page 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Reviews: