background image

3DJH 

Liquid Line

Set Diameter

Ozs. per 5 ft. (ml per mm) adjust

from 20 ft. (6096 mm) line set*

1/4 in.

(6mm)

1 ounce per 5 ft.

(30ml per 1524 mm)

3/8 in.

(10mm)

5/16 in.

(8mm)

2 ounce per 5 ft.

(60ml per 1524 mm)

3 ounce per 5 ft.

(90ml per 1524 mm)

*If line length is greater than 20 feet (6096 mm), add this amount.

If line length is less than 20 feet (6096 mm), subtract this amount.

TABLE 2

If the system is void of refrigerant, the recommended

and most accurate method of charging is to weigh the

refrigerant into the unit according to the total amount

shown on the unit nameplate. This may be done after

any leaks have been repaired. If weighing facilities

are not available or if unit is just low on charge, use

one of the procedures outlined.
Charging a heat pump is recommended during warm

weather. However, applications arise in which charg-

ing must occur in the colder months. The way the unit

is charged depends on the unit’s refrigerant metering

device and the outdoor ambient temperature.
For RFC systems, weighing in the charge and Subcool-

ing are two acceptable means of charging under certain

conditions. For installations of an RFC system where the

outdoor ambient is less than 60EF, weighing in the

charge is the best method. However, in installations

where the outdoor ambient is 60EF or above, subcool-

ing is the best method.
The Subcooling and the Approach methods are the

two recommended procedures for charging the HP23

using an expansion valve system for refrigerant me-

tering. The difference between the two involves the

outdoor ambient temperature. For expansion valve

systems where the outdoor ambient temperature is

60EF or above, the Approach method must be used.

For expansion valve systems where the outdoor am-

bient temperature is below 60EF, the subcooling

method should be used.
Before charging the unit, follow the procedure below

to determine: the liquid line temperature and the out-

door ambient temperature.

1-- Connect manifold gauge set to service valves: low

pressure gauge to vapor valve service port; high

pressure gauge to liquid valve service port. Con-

nect the center manifold hose to an upright bottle

of R22. Close manifold gauge set valves.

2-- Set the room thermostat to call for heat. This will

create the necessary load for properly charging

the system in the cooling cycle.

3-- Fill the thermometer well with mineral oil.
4-- Record the outdoor ambient temperature. For

greater accuracy, use the same thermometer to

measure liquid temperature.

5-- When thermostat demand has been satisfied,

switch to cooling mode with a set point of 68EF.

When pressures have stabilized, place the ther-

mometer in thermometer well and record the liq-

uid line temperature.

6-- The outdoor temperature will determine which

charging method to use. Proceed with the ap-

propriate charging procedure below.

NOTE--The model number “410” refers to both 411
(single--phase) and 413 (three--phase) units. The
same applies for 460 (461/463), 510 (511/513) and 650
(651/653) units.

&+$5*,1* )25 5)& 6<67(06

Weighing in the Charge Method
RFC Systems, < 60EF Outdoor Temp

  5HFRYHU WKH UHIULJHUDQW IURP WKH XQLW
  &RQGXFW D OHDN FKHFN WKHQ HYDFXDWH DV SUHYLRXVO\

RXWOLQHG

  :HLJK LQ WKH IDFWRU\ FKDUJH DV VKRZQ RQ WKH RXWGRRU

XQLWV UDWLQJ SODWH

The Subcooling Method

RFC Systems, > 60EF Outdoor Temp

  :LWK WKH PDQLIROG JDXJH KRVH VWLOO RQ WKH OLTXLG VHU

YLFH SRUW DQG WKH XQLW RSHUDWLQJ VWDEO\ UHFRUG WKH OLT
XLG OLQH WHPSHUDWXUH

  $W WKH VDPH WLPH UHFRUG WKH OLTXLG OLQH SUHVVXUH

UHDGLQJ

  8VLQJ D WHPSHUDWXUHSUHVVXUH FKDUW IRU 5 GHWHU

PLQH WKH VDWXUDWLRQ WHPSHUDWXUH IRU WKH OLTXLG OLQH
SUHVVXUH UHDGLQJ

  6XEWUDFW WKH OLTXLG OLQH WHPSHUDWXUH IURP WKH VDWXUD

WLRQ WHPSHUDWXUH DFFRUGLQJ WR WKH FKDUW WR GHWHU
PLQH VXEFRROLQJ /LTXLG OLQH WHPSHUDWXUH   6DWX
UDWLRQ WHPSHUDWXUH  6XEFRROLQJ

  &RPSDUH WKH VXEFRROLQJ YDOXH ZLWK WKRVH LQ WDEOH 

,I VXEFRROLQJ LV JUHDWHU WKDQ VKRZQ VRPH UHIULJHUDQW
PXVW EH UHFRYHUHG ,I VXEFRROLQJ LV OHVV WKDQ VKRZQ
VRPH UHIULJHUDQW PXVW EH DGGHG

Outdoor

Unit

Indoor

Unit

Ambient Temperatures _F

65 75 85 95 105 115

HP23--141
HP23--211
HP23--261

HP23--410

CB/CBH19--41

CB/CBH19--26

CB/CBH19--21

CB/CBH19--21

Subcooling at Various

CB/CBH19--31

CB/CBH19--41

HP23--311

HP23--460

TABLE 3

SUBCOOLING METHOD--RFCIII Systems

5

13
12
12

17
11

5

13
12
12

15
10

4

13
11
10

14

7

1

12

9
8

11

6

0
6
7
6

8
4

0
4
5
4

5
2

CB19--51

HP23--510

11 10 8 7

5

2

CB/CBH19--41

HP23--410CDN

13 12 10 8

6

3

&+$5*,1* )25 7;9 6<67(06

Summary of Contents for HP23-141

Page 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Page 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Page 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Page 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Page 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Page 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Page 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Page 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Page 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Page 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Page 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Page 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Reviews: