background image

3DJH 

VAPOR LINE SERVICE VALVE (VALVE OPEN)

FIGURE 9

SCHRADER VALVE

SERVICE PORT

SERVICE PORT

CAP

STEM CAP

SNAP RING

INSERT HEX

WRENCH HERE

VAPOR LINE SERVICE VALVE (VALVE CLOSED)

INLET

(FROM INDOOR COIL)

OUTLET (TO

COMPRESSOR)

KNIFE EDGE

SEAL

SCHRADER VALVE OPEN

TO LINE SET WHEN

VALVE IS CLOSED

(FRONT SEATED)

SERVICE PORT

SERVICE PORT

CAP

(VALVE FRONT

SEATED)

SNAP RING

STEM

CAP

OUTLET

(TO COMPRESSOR)

KNIFE EDGE SEAL

INLET

(FROM INDOOR COIL)

INSERT HEX

WRENCH HERE

Do not attempt to backseat this valve. Attempts to

backseat this valve will cause snap ring to explode

from valve body under pressure of refrigerant.

Personal injury and unit damage will result.

DANGER

3-- Replace stem cap tighten firmly. Tighten finger

tight, then tighten an additional 1/6 turn.

To Close Vapor Line Service Valve:

1-- Remove stem cap with an adjustable wrench.
2-- Using service wrench and 5/16” hex head exten-

sion, turn stem clockwise to seat the valve. Tight-

en firmly.

3-- Replace stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

/($. 7(67,1*

After the line set has been connected to the indoor

and outdoor units, the line set connections and in-

door unit must be checked for leaks.

WARNING

Never use oxygen to pressurize refrigeration or air

conditioning system. Oxygen will explode on con-

tact with oil and could cause personal injury.

When using high pressure gas such as nitrogen or

CO

2

for this purpose, be sure to use a regulator

that can control the pressure down to 1 or 2 psig.

Using an Electronic Leak Detector or Halide

1-- Connect a cylinder of nitrogen with a pressure reg-

ulating valve to the center port of the manifold

gauge set.

2-- Connect the high pressure hose of the manifold

gauge set to the service port of the vapor valve.

(Normally, the high pressure hose is connected to

the liquid line port, however, connecting it to the

vapor port better protects the manifold gauge set

from high pressure damage.)

3-- With both manifold valves closed, open the valve

on the R22 bottle (vapor only).

4-- Open the high pressure side of the manifold to al-

low R22 into the line set and indoor unit. Weigh in

a trace amount of R22. (A trace amount is a maxi-

mum of 2 ounces or 3 pounds pressure.) Close

the valve on the R22 bottle and the valve on the

high pressure side of the manifold gauge set. Dis-

connect R22 bottle.

5-- Adjust nitrogen pressure to 150 psig. Open the

valve on the high side of the manifold gauge set

which will pressurize line set and indoor unit.

6-- After a short period of time, open a refrigerant

port to make sure the refrigerant added is ade-

quate to be detected. (Amounts of refrigerant will

vary with line lengths.) Check all joints for leaks.

Purge nitrogen and R22 mixture. Correct any

leaks and recheck.

Summary of Contents for HP23-141

Page 1: ...HFODLPLQJ PXVW EH IROORZHG LQHV DQG RU LQFDUFHUDWLRQ PD EH OHYLHG IRU QRQ FRP SOLDQFH 167 7 21 16758 7 216 3 6 5 6 81 76 7 3803 81 76 WKURXJK WRQ 0 6XSHUVHGHV 0 7 2 217 176 3 7 3803 81 7 6 33 1 1 3 1...

Page 2: ...6WDWH 6HUYLFHPDQ PSV 6XSSO 2XWGRRU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 530 OHFWULFDO RQQHFWLRQV 7LJKW 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U 2XWGRRU RLO QWHULQJ LU 7HPSHUDWXUH LTXLG 3U...

Page 3: ...f a support frame is constructed it must not block drain holes in unit base 4 When installed in areas where low ambient tem peratures exist locate unit so winter prevailing winds do not blow directly...

Page 4: ...rafts or vibra tion Do not install thermostat on an outside wall A position approximately 5 feet 1524 mm from the floor and near the center of the conditioned area is most desirable 5 Route 24VAC cont...

Page 5: ...ne I D and O D 2 The thermometer well packaged separately and at tached to the liquid line should be installed in the liquid line close to the HP23 unit as shown in figure 5 Connect thermometer well m...

Page 6: ...NIFOLD GAUGE CONNECTIONS OUTDOOR COIL DEFROST THERMOSTAT EXPANSION VALVE FILTER DRIER WITH INTERNAL CHECK VALVE STRAINER TO R 22 DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REVERSING VALVE VAPOR LINE V...

Page 7: ...nect high pres sure gauge to service port 3 Using service wrench open valve stem one turn clockwise from backseated position 4 When finished using port backseat stem with ser vice wrench Tighten firml...

Page 8: ...n will explode on con tact with oil and could cause personal injury When using high pressure gas such as nitrogen or CO2 for this purpose be sure to use a regulator that can control the pressure down...

Page 9: ...ifold gauge valves to release the nitrogen from the line set and indoor unit 7 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit un...

Page 10: ...center manifold hose to an upright bottle of R22 Close manifold gauge set valves 2 Set the room thermostat to call for heat This will create the necessary load for properly charging the system in the...

Page 11: ...shown refrigerant must be reclaimed If Subcooling is less than shown refrigerant must be added TABLE 4 SUBCOOLING TEMP EF MODEL HP23 211 HP23 410 HP23 460 4 2 HP23 311 HP23 261 HP23 141 HP23 510 HP23...

Page 12: ...ill not allow a de frost to last for more than 14 minutes The defrost timer can be field adjusted from a 60 minute to a 30 or 90 minute defrost interval if warranted by climatic con ditions Timed Off...

Reviews: