background image

Page 19

TABLE 7

 Adding Charge per Indoor Unit Match using Subcooling Method

Use
cooling
mode

Use
heating
mode

1 Check the airflow as illustrated in figure20 to be sure the indoor airflow is as required.

(Make any air flow adjustments before continuing with the following procedure.)

2 Measure outdoor ambient temperature; determine whether to use 

cooling

 

mode

 or

heating mode

 to check charge.

3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating

Pressures table 5, (

Table 5 is a general guide. Expect minor pressure variations.

Significant differences may mean improper charge or other system problem.

)

5 Set thermostat for heat/cool demand, depending on mode being used:

Using cooling mode

When the outdoor ambient temperature is 60°F (15°C) and above.

Target subcooling values in table below are based on 70 to 80°F (21−27°C) indoor return
air temperature; if necessary, operate heating to reach that temperature range; then set
thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized,
continue with step 6.

Using heating mode

When the outdoor ambient temperature is below 60°F (15°C).

Target subcooling values in table below are based on 65−75°F (18−24°C) indoor return air
temperature; if necessary, operate cooling to reach that temperature range; then set
thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized,
continue with step 6.

6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/

pressure chart listed on page 20 and record it in the SATº space.

8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.

9 Compare SCº results with table below, being sure to note any additional charge for line

set and/or match−up.

10 If subcooling value is greater than shown in table, remove refrigerant; if less than shown,

add refrigerant.

11 If refrigerant is added or removed, repeat steps 5 through 10 to verify charge.

60ºF (15ºC)

SATº

LIQº

SCº

=

INDOOR

HEAT

MATCH−UP

PUMP

 Subcool Target
Cooling Heating
(+5ºF)

(+1ºF)

*Add

charge

INDOOR

HEAT

MATCH−UP

PUMP

 Subcool Target
Cooling Heating
(+5ºF)

(+1ºF)

*Add

charge

INDOOR

HEAT

MATCH−UP

PUMP

 Subcool Target
Cooling Heating
(+5ºF)

(+1ºF)

*Add

charge

XP14

018

lb oz

XP14

030 (cont’d)

lb oz

XP14

042 (cont’d)

lb oz

CBX27UH−018/024

13

7

0

8

CX34−31A/B

11

6

1

6

CX34−62C, −62D

12

6

0

9

CBX32MV−018/024

15

7

0

0

CX34−38A/B

11

6

2

3

CX34−49C

12

6

0

7

XP14

024

lb oz

CX34−43B/C

15

11

2

14

CX34−60D

12

6

0

4

CH23−41

16

8

0

2

XP14

036

lb oz

XP14

048

lb oz

CBX26UH−024

25

7

0

0

CBX26UH−036

26

5

0

0

CH23−68

20

9

2

9

CBX27UH−018/024

15

8

1

2

CBX26UH−037

25

4

1

9

CBX26UH−048

8

7

1

9

CBX32M−018/024

16

8

0

14

CBX27UH−036

13

6

0

3

CBX27UH−048

11

8

1

2

CBX32M−030

15

8

1

3

CBX32M−036

13

6

0

2

CBX32M−048, −060

11

8

1

2

CBX32MV−018/024

16

8

0

14

CBX32M−042

13

6

0

3

CBX32MV−048, −060

11

8

1

2

CBX32MV−024/030

15

8

1

2

CBX32MV−036

13

6

0

3

CBX32MV−068

10

7

1

12

CH33−42B

14

11

1

10

CBX32MV−048

11

8

2

5

CH33−50/60C

11

8

1

1

CH33−36A

16

8

1

0

C33−44C

13

6

0

0

CH33−62D

10

7

1

14

CH33−36C

16

8

0

4

CH33−50/60C

11

8

2

5

CH33−60D

11

8

0

0

CR33−30/36A/B/C

25

7

0

2

CH33−44B

13

6

1

7

CR33−50/60C

35

5

0

0

CX34−25A/B

16

8

0

14

CH33−48B

13

6

1

8

CR33−60D

37

6

0

0

CX34−31A/B

15

8

1

3

CR33−50/60C

25

4

1

15

CBX33−048, −060

12

8

1

2

CX34−36A/B/C

16

8

1

8

CR33−48B/C

25

5

0

9

CX34−62C, −62D

10

7

1

7

CX34−38A/B

14

11

2

2

CX34−49C

13

6

2

4

CX34−49D

11

8

0

14

XP14

030

lb oz

CX34−43B/C, −50/60C

13

6

1

8

CX34−60D

11

8

0

0

CH23−41

11

6

0

8

CX34−38A/B, −44/48C

13

6

0

0

XP14

060

lb oz

CH23−51

6

6

1

12

XP14

042

lb oz

CH23−68

12

5

0

0

CBX26UH−024

30

8

0

6

CH23−68

20

9

0

13

CBX26UH−048

12

7

1

0

CBX26UH−030

29

8

2

3

CBX26UH−042

27

6

0

0

CBX26UH−060

14

4

0

0

CBX27UH−030

11

6

2

4

CBX27UH−042

12

6

0

8

CBX27UH−060

12

5

0

0

CBX32M−030

11

6

1

6

CBX32M−048

12

6

0

7

CBX32M−048, −060

12

5

0

0

CBX32M−036

11

6

2

4

CBX32MV−048

12

6

0

8

CBX32MV−048, −060

12

5

0

0

CBX32MV−024/030

11

6

1

6

CH33−62D

12

6

0

10

CBX32MV−068

12

7

1

0

CBX32MV−036

11

6

2

4

CH33−50/60C

12

6

0

7

CH33−50/60C

12

5

0

0

C33−44C

11

6

2

3

CH33−60D

12

6

0

4

CH33−62D

12

5

0

0

CH33−36C

11

3

0

0

CR33−50/60C,−60D

26

6

0

4

CBX33−060

12

8

0

0

CH33−42B

6

6

1

12

CBX33−042,−048

12

7

0

4

CX34−62C, −62D

12

7

1

0

CR33−30/36A/B/C

30

8

0

8

CBX33−060

12

6

0

7

*Add charge = Extra match−up amount required in addition to charge indicated on Heat Pump nameplate (remember to also add any charge required for line set differ-
ences from 15 feet).

Summary of Contents for Elite XP14018

Page 1: ...ated for HFC 410A WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or insta...

Page 2: ...t protection amps 20 30 30 30 40 50 60 3 Minimum circuit ampacity 11 9 17 5 17 0 19 4 24 2 29 34 8 Compressor Rated Load Amps 8 97 13 46 13 1 14 1 17 94 21 79 26 41 p Locked Rotor Amps 48 58 64 77 112...

Page 3: ...OR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP14 units are not equipped wi...

Page 4: ...g con ditions during the defrost cycle and 90 seconds after the termina tion of defrost when the average ambient sensor temperature is below 15 F 9 C for 90 seconds following the start up of the compr...

Page 5: ...cted as being open shorted or out of the temperature range of the sensor the control will not perform demand de frost operation The control will revert to time temperature defrost operation and will d...

Page 6: ...l attempt to self calibrate after this and all other de frost cycle s Calibration success depends on stable system tempera tures during the 20 minute calibration period If the control fails to calibra...

Page 7: ...horted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re applied If no fault exists and ambient temperature...

Page 8: ...Valve ON W1 line ON Monitor coil temperature and time in defrost mode HOW DID DEFROST TERMINATE Coil temperature was above 35 F 2 C for 4 min of the 14 min de frost OR reached defrost termination tem...

Page 9: ...hat control has internal component failure Cycle 24 volt power to control If code does not clear replace control FAULT LOCKOUT CODES Each fault adds 1 strike to that code s counter 5 strikes per code...

Page 10: ...ll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties Figure 11 shows the basic scroll form Two identical scrolls are mated together form...

Page 11: ...nventional Lennox cleanup practices must be used Due to its efficiency the scroll compressor is capable of draw ing a much deeper vacuum than reciprocating compres sors Deep vacuum operation can cause...

Page 12: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 13: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 14: ...ustable wrench 2 Use a service wrench with a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for...

Page 15: ...10A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose to the vapor valve serv...

Page 16: ...nute period after shutting off the vacuum pump and closing the manifold gauge valves 9 When the absolute pressure requirement above has been met disconnect the manifold hose from the vacu um pump and...

Page 17: ...within 3 DT 80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20...

Page 18: ...387 146 397 145 369 146 374 142 384 146 401 143 105 41 402 148 412 147 424 147 394 147 399 143 411 148 426 145 110 38 430 149 441 148 454 150 421 148 428 145 439 149 452 146 115 45 465 150 471 151 48...

Page 19: ...PUMP Subcool Target Cooling Heating 5 F 1 F Add charge INDOOR HEAT MATCH UP PUMP Subcool Target Cooling Heating 5 F 1 F Add charge XP14 018 lb oz XP14 030 cont d lb oz XP14 042 cont d lb oz CBX27UH 0...

Page 20: ...OE oils used with HFC 410A refrig erant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve s...

Page 21: ...cooling the unit should be gauged and refrigerant charge checked Refer to section on refrigerant charging in this instruction 1 Clean and inspect condenser coil Coil may be flushed with a water hose a...

Page 22: ...Page 22 VII WIRING DIAGRAM AND SEQUENCE OF OPERATION XP14 UNIT DIAGRAM 5 1 2 3 4 6...

Page 23: ...l thermostat wiring de energizes terminal O by heat ing mode selection de energizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE Whena defrost c...

Reviews: