background image

Page 12

ALIGN FAN HUB FLUSH WITH END OF SHAFT

FIGURE 15

NUTS (4)

D − Reversing Valve L1 and Solenoid

A refrigerant reversing valve with electromechanical so-
lenoid is used to reverse refrigerant flow during unit op-
eration. The reversing valve requires no maintenance. It
is not repairable. If the reversing valve has failed, it must
be replaced.

E − Drier

A filter drier designed for all XP14 model units is factory
installed in the liquid line. The filter drier is designed to re-
move moisture and foreign matter, which can lead to com-
pressor failure.

Moisture and  / or Acid Check

 

Because POE oils absorb moisture, the dryness of the

system must be verified any time the refrigerant sys-
tem is exposed to open air. 

A

 

compressor oil sample must

be taken to determine if 

excessive

 moisture has been

introduced to the oil. Table 3 lists kits available from Lennox
to check POE oils.

If oil sample taken from a system that has been exposed to
open air does not test in the dry color range, the filter drier
MUST be replace.

To safeguard against moisture entering the system follow
the steps in section IV −  sub section B − "Evacuating the
System" when replacing the drier.

IMPORTANT

Replacement filter drier MUST be approved for
HFC−410A refrigerant and POE application.

F − High (S4)/Low (S87) Pressure Switch

IMPORTANT

Pressure switch settings for HFC−410A refrigerant
will be significantly higher than units with
HCFC−22.

An auto-reset, single-pole/single-throw high pressure switch
is located in the liquid line. This switch shuts off  the compres-
sor when liquid line pressure rises above the factory setting.
The switch is normally closed and is permanently adjusted to
trip (open) at 590 + 10 psi.

An auto-reset, single-pole/single-throw low pressure
switch is located in the suction line. This switch shuts off the
compressor when suction pressure drops below the factory
setting. The switch is closed during normal operating pres-
sure conditions and is permanently adjusted to trip (open)
at 25 + 5 psi. The switch automatically resets when suction
line pressure rises above 40 + 5 psi. Under certain condi-
tions the low pressure switch is ignored. See 

Pressure

Switch Circuit 

in the Defrost  Control description.

G − Crankecase Heater (HR1) &

Thermostat (S40)

XP14−036, −042, −048 and −060 units are equipped with a 40
watt belly band type crankcase heater. HR1 prevents liquid
from accumulating in the compressor. HR1 is controlled by
a thermostat located on the liquid line. When liquid line tem-
perature drops below 50° F the thermostat closes energiz-
ing HR1. The thermostat will open, de−energizing HR1
once liquid line temperature reaches 70° F.

TABLE 3

KIT

CONTENTS

TUBE SHELF LIFE

10N46 − Refrigerant Analysis

Checkmate−RT700

10N45 − Acid Test Tubes

Checkmate−RT750A (three pack)

2 − 3 years @ room temperature. 3+
years refrigerated

10N44 − Moisture Test Tubes

Checkmate − RT751 Tubes (three
pack)

6 − 12 months @ room temperature. 2
years refrigerated

74N40 − Easy Oil Test Tubes

Checkmate − RT752C Tubes (three
pack)

2 − 3 years @ room temperature. 3+
years refrigerated

74N39 − Acid Test Kit

Sporian One Shot − TA−1

Summary of Contents for Elite XP14018

Page 1: ...ated for HFC 410A WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or insta...

Page 2: ...t protection amps 20 30 30 30 40 50 60 3 Minimum circuit ampacity 11 9 17 5 17 0 19 4 24 2 29 34 8 Compressor Rated Load Amps 8 97 13 46 13 1 14 1 17 94 21 79 26 41 p Locked Rotor Amps 48 58 64 77 112...

Page 3: ...OR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP14 units are not equipped wi...

Page 4: ...g con ditions during the defrost cycle and 90 seconds after the termina tion of defrost when the average ambient sensor temperature is below 15 F 9 C for 90 seconds following the start up of the compr...

Page 5: ...cted as being open shorted or out of the temperature range of the sensor the control will not perform demand de frost operation The control will revert to time temperature defrost operation and will d...

Page 6: ...l attempt to self calibrate after this and all other de frost cycle s Calibration success depends on stable system tempera tures during the 20 minute calibration period If the control fails to calibra...

Page 7: ...horted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re applied If no fault exists and ambient temperature...

Page 8: ...Valve ON W1 line ON Monitor coil temperature and time in defrost mode HOW DID DEFROST TERMINATE Coil temperature was above 35 F 2 C for 4 min of the 14 min de frost OR reached defrost termination tem...

Page 9: ...hat control has internal component failure Cycle 24 volt power to control If code does not clear replace control FAULT LOCKOUT CODES Each fault adds 1 strike to that code s counter 5 strikes per code...

Page 10: ...ll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties Figure 11 shows the basic scroll form Two identical scrolls are mated together form...

Page 11: ...nventional Lennox cleanup practices must be used Due to its efficiency the scroll compressor is capable of draw ing a much deeper vacuum than reciprocating compres sors Deep vacuum operation can cause...

Page 12: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 13: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 14: ...ustable wrench 2 Use a service wrench with a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for...

Page 15: ...10A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose to the vapor valve serv...

Page 16: ...nute period after shutting off the vacuum pump and closing the manifold gauge valves 9 When the absolute pressure requirement above has been met disconnect the manifold hose from the vacu um pump and...

Page 17: ...within 3 DT 80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20...

Page 18: ...387 146 397 145 369 146 374 142 384 146 401 143 105 41 402 148 412 147 424 147 394 147 399 143 411 148 426 145 110 38 430 149 441 148 454 150 421 148 428 145 439 149 452 146 115 45 465 150 471 151 48...

Page 19: ...PUMP Subcool Target Cooling Heating 5 F 1 F Add charge INDOOR HEAT MATCH UP PUMP Subcool Target Cooling Heating 5 F 1 F Add charge XP14 018 lb oz XP14 030 cont d lb oz XP14 042 cont d lb oz CBX27UH 0...

Page 20: ...OE oils used with HFC 410A refrig erant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve s...

Page 21: ...cooling the unit should be gauged and refrigerant charge checked Refer to section on refrigerant charging in this instruction 1 Clean and inspect condenser coil Coil may be flushed with a water hose a...

Page 22: ...Page 22 VII WIRING DIAGRAM AND SEQUENCE OF OPERATION XP14 UNIT DIAGRAM 5 1 2 3 4 6...

Page 23: ...l thermostat wiring de energizes terminal O by heat ing mode selection de energizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE Whena defrost c...

Reviews: