background image

Page 4

2 − Dual Capacitor C12

The compressor and fan in XP14 series units use permanent
split capacitor motors. The capacitor is located inside the unit
control box (see figure 2). A single dual" capacitor (C12) is
used for both the fan motor and the compressor (see unit wir-
ing diagram). The fan side and the compressor side of the ca-
pacitor have different MFD ratings. See side of capacitor for
ratings.

3 − Defrost System (CMC1)

The demand defrost control measures differential temper-
atures to detect when the system is performing poorly be-
cause of ice build−up on the outdoor coil. The controller
self−calibrates" when the defrost system starts and after
each system defrost cycle. The defrost control compo-
nents are shown in figure 4.

The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a de-
frost cycle is required. The coil temperature probe is de-
signed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.

NOTE − The demand defrost control accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the board initiates defrost cycles.

Diagnostic LEDs

The state (Off, On, Flashing) of two LEDs on the defrost
board (DS1 [Red] and DS2 [Green]) indicate diagnostics
conditions that are described in table 2.

24V TERMINAL
STRIP
CONNECTIONS

DIAGNOSTIC
LEDS

PRESSURE

SWITCH CIRCUIT

CONNECTIONS

TEST PINS

NOTE − Component Locations Vary by Control Manufacturer.

Y2 not used on XP14

SENSOR

PLUG IN

(COIL & AM-

BIENT

SENSORS)

REVERSING

VALVE

DELAY

PINS

LOW
AMBIENT
THERMOSTAT
PINS

DEFROST

TERMINATION

PIN SETTINGS

FIGURE 4

Defrost Control Pressure Switch Connections

The unit’s automatic reset pressure switches (LO PS − S87
and HI PS − S4) are factory−wired into the defrost control on
the LO−PS and HI−PS terminals, respectively.

Low Pressure Switch (LO−PS)

When the low pressure

switch trips, the defrost control will cycle off the compressor,
and the strike counter in the control will count one strike.
The low pressure switch is ignored under the following con-
ditions:
during the defrost cycle and 90 seconds after the termina-

tion of defrost

when the average ambient sensor temperature is below

15° F (−9°C)

for 90 seconds following the start up of the compressor
during "test" mode

High Pressure Switch (HI−PS)

When the high pressure

switch trips, the defrost control will cycle off the compressor,
and the strike counter in the control will count one strike.

Defrost Control Pressure Switch Settings

High Pressure

  (auto reset) − trip at 590 psig; reset at 418.

Low Pressure

 (auto reset) − trip at 25 psig; reset at 55.

5−Strike Lockout Feature

The internal control logic of the control counts the pressure
switch trips only while the Y1 (Input) line is active. If a pres-
sure switch opens and closes four times during a Y1 (Input),
the control logic will reset the pressure switch trip counter to
zero at the end of the Y1 (Input). If the pressure switch
opens for a fifth time during the current Y1 (Input), the con-
trol will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset
by cycling OFF the 24−volt power to the control board or by
shorting the TEST pins between 1 and 2 seconds. All timer
functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged,
a 5−minute short cycle will occur after the switch closes.

Defrost System Sensors

Sensors connect to the defrost control through a field-re-
placeable harness assembly that plugs into the board.
Through the sensors, the control detects outdoor ambient
and coil temperature fault conditions. As the detected tem-
perature changes, the resistance across the sensor
changes. Figure 5 shows how the resistance varies as the
temperature changes for both type of sensors. Sensor re-
sistance values can be checked by ohming across pins
shown in table 1.

TABLE 1

Sensor

Temperature
Range °F (°C)

Resistance values
range (ohms)

Pins/Wire
Color

Outdoor
(Ambient)

−35 (−37) to 120
(48)

280,000 to 3750

3 & 4
(Black)

Coil

−35 (−37) to 120
(48)

280,000 to 3750

5 & 6
(Brown)

Discharge (if
applicable)

24 (−4) to 350
(176)

41,000 to 103

1 & 2
(Yellow)

Note: Sensor resistance decreases as sensed temperature increases
(see figure5).

NOTE − When checking the ohms across a sensor, be
aware that a sensor showing a resistance value that is not
within the range shown in table 1, may be performing as de-
signed. However, if a shorted or open circuit is detected,
then the sensor may be faulty and the sensor harness will
needs to be replaced.

Summary of Contents for Elite XP14018

Page 1: ...ated for HFC 410A WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or insta...

Page 2: ...t protection amps 20 30 30 30 40 50 60 3 Minimum circuit ampacity 11 9 17 5 17 0 19 4 24 2 29 34 8 Compressor Rated Load Amps 8 97 13 46 13 1 14 1 17 94 21 79 26 41 p Locked Rotor Amps 48 58 64 77 112...

Page 3: ...OR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP14 units are not equipped wi...

Page 4: ...g con ditions during the defrost cycle and 90 seconds after the termina tion of defrost when the average ambient sensor temperature is below 15 F 9 C for 90 seconds following the start up of the compr...

Page 5: ...cted as being open shorted or out of the temperature range of the sensor the control will not perform demand de frost operation The control will revert to time temperature defrost operation and will d...

Page 6: ...l attempt to self calibrate after this and all other de frost cycle s Calibration success depends on stable system tempera tures during the 20 minute calibration period If the control fails to calibra...

Page 7: ...horted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re applied If no fault exists and ambient temperature...

Page 8: ...Valve ON W1 line ON Monitor coil temperature and time in defrost mode HOW DID DEFROST TERMINATE Coil temperature was above 35 F 2 C for 4 min of the 14 min de frost OR reached defrost termination tem...

Page 9: ...hat control has internal component failure Cycle 24 volt power to control If code does not clear replace control FAULT LOCKOUT CODES Each fault adds 1 strike to that code s counter 5 strikes per code...

Page 10: ...ll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties Figure 11 shows the basic scroll form Two identical scrolls are mated together form...

Page 11: ...nventional Lennox cleanup practices must be used Due to its efficiency the scroll compressor is capable of draw ing a much deeper vacuum than reciprocating compres sors Deep vacuum operation can cause...

Page 12: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Page 13: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Page 14: ...ustable wrench 2 Use a service wrench with a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for...

Page 15: ...10A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose to the vapor valve serv...

Page 16: ...nute period after shutting off the vacuum pump and closing the manifold gauge valves 9 When the absolute pressure requirement above has been met disconnect the manifold hose from the vacu um pump and...

Page 17: ...within 3 DT 80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20...

Page 18: ...387 146 397 145 369 146 374 142 384 146 401 143 105 41 402 148 412 147 424 147 394 147 399 143 411 148 426 145 110 38 430 149 441 148 454 150 421 148 428 145 439 149 452 146 115 45 465 150 471 151 48...

Page 19: ...PUMP Subcool Target Cooling Heating 5 F 1 F Add charge INDOOR HEAT MATCH UP PUMP Subcool Target Cooling Heating 5 F 1 F Add charge XP14 018 lb oz XP14 030 cont d lb oz XP14 042 cont d lb oz CBX27UH 0...

Page 20: ...OE oils used with HFC 410A refrig erant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve s...

Page 21: ...cooling the unit should be gauged and refrigerant charge checked Refer to section on refrigerant charging in this instruction 1 Clean and inspect condenser coil Coil may be flushed with a water hose a...

Page 22: ...Page 22 VII WIRING DIAGRAM AND SEQUENCE OF OPERATION XP14 UNIT DIAGRAM 5 1 2 3 4 6...

Page 23: ...l thermostat wiring de energizes terminal O by heat ing mode selection de energizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE Whena defrost c...

Reviews: