GENERAL
This XP14 outdoor heat pump is designed for use with
HFC-410A refrigerant only. This unit must be installed
with an approved indoor air handler or coil. See the Len
nox XP14 Product Specifications bulletin (EHB) for ap
proved indoor component match ups.
These instructions are intended as a general guide and
do not supersede local codes in any way. Consult authori
ties having jurisdiction before installation.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
INSTALLATION
INSTRUCTIONS
Elite
®
Series XP14 Units
HEAT PUMP
507362-01
8/2015
Supersedes 7/2014
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal in
jury or loss of life.
Installation and service must be performed by a li
censed professional installer (or equivalent) or service
agency.
NOTICE !
Charging information is given on the charging pro
cedure sticker on the unit access panel. For more
in-depth information, consult the Installation and
Service Procedures manual, available as Corp.
0721-L7 on DaveNet or through the Technical Sup
port department at 800-453-6669.
STEP 1 -- SETTING THE UNIT -- Clearances
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
See
NOTES
See NOTES
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of
the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in (914 mm).
Clearance to one of the remaining two sides may be 12 in. (305mm)
and the final side may be 6 in.(152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.