STEP 3 −− INSTALLING INDOOR EXPANSION VALVE 

This outdoor unit is designed for use in systems that include an check/expansion valve metering device. See the

 XP13

Product Specifications bulletin (EHB)

 for approved check/expansion valve kit match−ups and application information. The

check/expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the check/expansion valve in a manner that will provide access for future field
service of the check expansion valve. Refer to below illustration for reference during installation of check/expansion valve.

 A.

Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.

NOTE 

 Confirm proper thermal contact between vapor line

and check expansion bulb before insulating the sensing bulb
once installed.

 B.

Connect the equalizer line from the check expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
below.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR
FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

CHECK

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

 C.

Install one of the provided Teflon

®

 rings around the

stubbed end of the check expansion valve and lightly
lubricate the connector threads and expose surface of
the Teflon

®

 ring with refrigerant oil.

 D.

Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or or tighten
to 20 ft−lb.

 E.

Place the remaining Teflon

®

 washer around the other

end of the check expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon

®

ring with refrigerant oil.

 F.

Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in the figure above or tighten to 20 ft−lb.

ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.

12

BULB

VAPOR LINE

VAPOR LINE

NOTE  NEVER MOUNT THE SENSING BULB

ON BOTTOM OF LINE.

BULB

BULB

BULB

VAPOR LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 Turn

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

1

2

3

4

5

6

7

8

9

10

11 12

1/8 Turn

 A.

Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure below.

 B.

Remove the field−provided fitting that temporarily recon-
nected the liquid line to the indoor unit’s distributor assemb-
ly.

INDOOR EXPANSION VALVE INSTALLATION

FIGURE 8

Summary of Contents for Elite XP13-018-230

Page 1: ...Units HEAT PUMP UNITS 506728 01 7 2012 Supersedes 3 2012 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installat...

Page 2: ...XP13 018 AND 024 BASE SECTION SMALL 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 13 7 8 352 K J UNIT SUPPORT FEET XP13 030 TO 060 BASE WITH ELONGATED LEGS MEDIUM 7 3 4 197 3 1 4 83 27 1 8 689 3...

Page 3: ...E SET VIBRATION Install unit away from windows FIGURE 2 Install unit level or if on a slope maintain slope tolerance of 2 degrees or 2 inches per 5 feet 50 mm per 1 5 m away from building structure SL...

Page 4: ...all existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the...

Page 5: ...ve and the two Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLIND...

Page 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE POR...

Page 7: ...ths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Page 8: ...UT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring...

Page 9: ...ect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A...

Page 10: ...nd closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned t...

Page 11: ...r damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service...

Page 12: ...GH VOLTAGE CIRCUITS A B C D 3 FIGURE 12 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLO...

Page 13: ...defrost mode The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second compressor feature is ignored when j...

Page 14: ...Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temp...

Page 15: ...he inside air Have your dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the ComfortSe...

Reviews: