Page 5

 XP13 SERIES

STEP 2 −− REFRIGERANT PIPING −− Removing Existing Indoor Metering Device

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

 A.

On fully cased coils, remove the coil access and plumbing panels.

 B.

Remove any shipping clamps from the liquid line and distributor as-
sembly.

 C.

Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro-
cess.

 D.

Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon

®

 washer as illustrated above.

 E.

Use a field−provided fitting to temporarily reconnect the liquid line to the
indoor unit’s liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE 
(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)

TWO−PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

CHECK

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

 A.

On fully cased coils, remove the coil access and plumbing panels.

 B.

Remove any shipping clamps from the liquid line and distributor
assembly.

 C.

Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.

 D.

Remove the vapor line sensing bulb.

 E.

Disconnect the liquid line from the check expansion valve at the
liquid line assembly.

 F.

Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during
this process.

 G.

Remove and discard check expansion valve and the two Teflon

®

rings.

 H.

Use a field−provided fitting to temporarily reconnect the liquid line to
the indoor unit’s liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING
CLEAN HCFC−22 TO BE USED
FOR FLUSHING
(Positioned to deliver liquid
refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

V

APOR

LIQUID

1

 A.

HCFC−22 cylinder with clean refrigerant (positioned to deliver liquid
refrigerant) to the vapor service valve.

 B.

HCFC−22 gauge set (low side) to the liquid line valve.

 C.

HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.

 D.

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

 A.

Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.

 B.

Position the cylinder of clean HCFC−22 for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.

 C.

After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.

 D.

Close the valve on the inverted HCFC−22 drum and the gauge set
valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant that previously charged the system. Check
the charge in the flushing cylinder before proceeding.

1A

2

3

1B

FIGURE 6

Summary of Contents for Elite XP13-018-230

Page 1: ...Units HEAT PUMP UNITS 506728 01 7 2012 Supersedes 3 2012 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installat...

Page 2: ...XP13 018 AND 024 BASE SECTION SMALL 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 13 7 8 352 K J UNIT SUPPORT FEET XP13 030 TO 060 BASE WITH ELONGATED LEGS MEDIUM 7 3 4 197 3 1 4 83 27 1 8 689 3...

Page 3: ...E SET VIBRATION Install unit away from windows FIGURE 2 Install unit level or if on a slope maintain slope tolerance of 2 degrees or 2 inches per 5 feet 50 mm per 1 5 m away from building structure SL...

Page 4: ...all existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the...

Page 5: ...ve and the two Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLIND...

Page 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE POR...

Page 7: ...ths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Page 8: ...UT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring...

Page 9: ...ect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A...

Page 10: ...nd closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned t...

Page 11: ...r damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service...

Page 12: ...GH VOLTAGE CIRCUITS A B C D 3 FIGURE 12 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLO...

Page 13: ...defrost mode The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second compressor feature is ignored when j...

Page 14: ...Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temp...

Page 15: ...he inside air Have your dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the ComfortSe...

Reviews: