background image

Page 10

STEP 4 −− LEAK TEST AND EVACUATION (Continued)

A

Open both manifold valves and start the vacuum pump.

B

Evacuate the line set and indoor unit to an 

absolute pressure

 of 23,000 microns (29.01 inches of mercury).

NOTE 

 During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a

relatively large leak. If this occurs, 

repeat the leak testing procedure

.

NOTE 

 The term 

absolute pressure

 means the total actual pressure above absolute zero within a given volume or system. Absolute pressure

in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C

When the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following:

S

Close manifold gauge valves.

S

Close valve on vacuum pump.

S

Turn off vacuum pump.

S

Disconnect manifold gauge center port hose from vacuum pump.

S

Attach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.

S

Open manifold gauge valves to break the vacuum in the line set and indoor
unit.

S

Close manifold gauge valves.

D

Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.

E

Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing
the manifold gauge valves.

F

When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC−410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line
set and indoor unit.

G

Perform the following:

S

Close manifold gauge valves.

S

Shut off HFC−410A cylinder.

S

Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.

S

Replace stem caps and finger tighten them, then tighten an additional one−sixth (1/6) of a turn as illustrated.

OUTDOOR

UNIT

TO VAPOR

SERVICE VALVE

TO LIQUID LINE
SERVICE VALVE

MICRON

GAUGE

VACUUM PUMP

1/4 SAE TEE WITH SWIVEL
COUPLER

500

MANIFOLD

GAUGE SET

HFC−410A

RECOMMEND

MINIMUM 3/8" HOSE

A

Connect low side of manifold gauge set with
1/4 SAE in−line tee to 

vapor 

line service valve

B

Connect high side of manifold gauge set to

liquid 

line service valve

C

Connect available micron gauge connector
on the 1/4 SAE in−line tee.

D

Connect the vacuum pump (with vacuum
gauge) to the center port of the manifold
gauge set. The center port line will be used
later for both the HFC−410A and nitrogen
containers.

HIGH

LOW

1

2

3

4

5

6

7

8

9

10

11 12

1/6 TURN

NITROGEN

3

CONNECT GAUGE SET

A

B

C

D

4

EVACUATE THE SYSTEM

NOTE 

 Remove cores from service valves (if not already done).

Possible equipment damage.

Avoid deep vacuum operation. Do not use
compressors to evacuate a system.
Extremely low vacuum can cause internal
arcing and compressor failure. Damage
caused by deep vacuum operation will
void warranty.

WARNING !

NOTE − Position
canister to deliver
liquid refrigerant.

EVACUATION

FIGURE 10

Summary of Contents for Elite XP13-018-230

Page 1: ...Units HEAT PUMP UNITS 506728 01 7 2012 Supersedes 3 2012 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installat...

Page 2: ...XP13 018 AND 024 BASE SECTION SMALL 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 13 7 8 352 K J UNIT SUPPORT FEET XP13 030 TO 060 BASE WITH ELONGATED LEGS MEDIUM 7 3 4 197 3 1 4 83 27 1 8 689 3...

Page 3: ...E SET VIBRATION Install unit away from windows FIGURE 2 Install unit level or if on a slope maintain slope tolerance of 2 degrees or 2 inches per 5 feet 50 mm per 1 5 m away from building structure SL...

Page 4: ...all existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the...

Page 5: ...ve and the two Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLIND...

Page 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE POR...

Page 7: ...ths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Page 8: ...UT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring...

Page 9: ...ect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A...

Page 10: ...nd closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned t...

Page 11: ...r damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service...

Page 12: ...GH VOLTAGE CIRCUITS A B C D 3 FIGURE 12 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLO...

Page 13: ...defrost mode The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second compressor feature is ignored when j...

Page 14: ...Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temp...

Page 15: ...he inside air Have your dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the ComfortSe...

Reviews: