background image

Page 15

 XP13 SERIES

Homeowners Information

Cleaning of the outdoor unit’s coil should be performed by
a licensed professional service technician (or equivalent).
Contact your dealer and set up a schedule (preferably
twice a year, but at least once a year) to inspect and ser-
vice your outdoor unit. The following maintenance may be
performed by the homeowner.

IMPORTANT !

Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.

Outdoor Coil

The outdoor unit must be properly maintained to ensure its
proper operation.

S

Please contact your dealer to schedule proper inspec-
tion and maintenance for your equipment.

S

Make sure no obstructions restrict airflow to the outdoor
unit.

S

Grass clippings, leaves, or shrubs crowding the unit can
cause the unit to work harder and use more energy.

S

Keep shrubbery trimmed away from the unit and periodi-
cally check for debris which collects around the unit.

S

Keep snow level below the louvered panels to ensure
proper performance.

Routine Maintenance

In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.

NOTE 

 The filter and all access panels must be in place

any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.

S

Ask your Lennox dealer to show you where your indoor
unit’s filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind
a return air grille in the wall or ceiling. Check the filter
monthly and clean or replace it as needed.

S

Disposable filters should be replaced with a filter of the
same type and size.

S

The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show
you the location of the drain line and how to check for

obstructions. (This would also apply to an auxiliary
drain, if installed.)

Thermostat Operation

See the ComfortSense

®

 7000 thermostat homeowner

manual for instructions on how to operate your thermostat.

Heat Pump Operation

Your new Lennox heat pump has several characteristics
that you should be aware of:

S

Heat pumps satisfy heating demand by delivering
large amounts of 

warm

 air into the living space. This

is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of consid-
erably 

hotter

 air to heat the space.

S

Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45

F (7

C). An electronic control activates a de-

frost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.

S

During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the de-
frost cycle to satisfy a heating demand; however, the
unit will return to normal operation at the conclusion of
the defrost cycle.

Extended Power Outage

The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant

slugging 

during cold weather operation.

If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the EMER-
GENCY HEAT setting to obtain temporary heat without the
risk of serious damage to the heat pump.

In EMERGENCY HEAT mode, all heating demand is satis-
fied by auxiliary heat; heat pump operation is locked out.
After a six-hour compressor crankcase warm-up period,
the thermostat can be switched to the HEAT setting and
normal heat pump operation may resume.

Preservice Check

If your system fails to operate, check the following before
calling for service:

S

Verify room thermostat settings are correct.

S

Verify that all electrical disconnect switches are ON.

S

Check for any blown fuses or tripped circuit breakers.

S

Verify unit access panels are in place.

S

Verify air filter is clean.

S

If service is needed, locate and write down the unit
model number and have it handy before calling.

Summary of Contents for Elite XP13-018-230

Page 1: ...Units HEAT PUMP UNITS 506728 01 7 2012 Supersedes 3 2012 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installat...

Page 2: ...XP13 018 AND 024 BASE SECTION SMALL 8 3 4 222 5 1 2 140 9 1 2 241 8 1 4 210 13 1 2 343 13 7 8 352 K J UNIT SUPPORT FEET XP13 030 TO 060 BASE WITH ELONGATED LEGS MEDIUM 7 3 4 197 3 1 4 83 27 1 8 689 3...

Page 3: ...E SET VIBRATION Install unit away from windows FIGURE 2 Install unit level or if on a slope maintain slope tolerance of 2 degrees or 2 inches per 5 feet 50 mm per 1 5 m away from building structure SL...

Page 4: ...all existing traps Polyol es ter POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the...

Page 5: ...ve and the two Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLIND...

Page 6: ...d debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE POR...

Page 7: ...ths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Page 8: ...UT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring...

Page 9: ...ect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A...

Page 10: ...nd closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned t...

Page 11: ...r damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service...

Page 12: ...GH VOLTAGE CIRCUITS A B C D 3 FIGURE 12 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLO...

Page 13: ...defrost mode The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second compressor feature is ignored when j...

Page 14: ...Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temp...

Page 15: ...he inside air Have your dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the ComfortSe...

Reviews: