1. Determine the desired 

D

T

Measure entering air temperature

using dry bulb (

A

) and wet bulb (

B

). 

D

T

 is the intersecting value of 

A

and

 B

 in the table (see triangle).

2. Find temperature drop across coil

Measure the coil’s dry bulb

entering and leaving air temperatures (

A

 and 

C

). Temperature Drop

Formula: (

T

Drop

) = 

A

 minus 

C

.

3. Determine if fan needs adjustment

If the difference between the

measured 

T

Drop

 and the desired 

D

T

 

(T

Drop

D

T) 

is 3º, no

adjustment is needed. See examples: Assume 

D

T

 = 15 and 

A

 temp. =

72º, these 

temperatures would necessitate stated actions:

Cº T

Drop

D

T

=

ºF

ACTION

53º

 19

15

=

4

Increase the airflow

58º

14

15

=

−1

(3º range) no change

62º

10

15

=

−5

Decrease the airflow

4. Adjust the fan speed

See indoor unit instructions to

increase/decrease fan speed.

Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and 

D

T are 3º.

D

T

80

24 24 24 23 23 22 22 22 20 19 18 17 16 15

78

23 23 23 22 22 21 21 20 19 18 17 16 15 14

76

22 22 22 21 21 20 19 19 18 17 16 15 14 13

74

21 21 21 20 19 19 18 17 16 16 15 14 13 12

72

20 20 19 18 17 17 16 15 15 14 13 12 11 10

70

19 19 18 18 17 17 16 15 15 14 13 12 11 10

57 58 59 60 61 62 63 64 65 66 67 68 69 70

Temp.
of air
entering
indoor
coil ºF

INDOOR
COIL

DRY

BULB

DRY

BULB

WET

BULB

B

T

Drop

19º

A

Dry−bulb

Wet−bulb ºF

A

72º

B

64º

C

53º

air flow

air flow

All temperatures are

expressed in ºF

INDOOR COIL AIRFLOW CHECK

Check indoor coil airflow using the Delta−T (

D

T)

 process as illustrated.

Figure 33. Indoor Coil Airflow Check

Charging System

WHEN TO CHARGE?

Warm weather best

Can charge in colder weather

CHARGE METHOD?

 Determine by:

Metering device type

Outdoor ambient temperature

REQUIREMENTS:

Sufficient heat load in structure

Indoor temperature between 70-80ºF
(21−26ºC)

Manifold gauge set connected to unit

Thermometers:

to measure outdoor ambient  temperature

to measure liquid line temperature

to measure suction line temperature

TXV

FIXED

ORIFICE

APPROACH OR

SUBCOOLING

WEIGH-IN

SUPERHEAT

65ºF

(18.3ºC) and

Above

START: Determine how refrigerant is metered

39ºF

(3.8ºC) and

Below

Which indoor

metering

device?

WEIGH-IN

64ºF

(17.7ºC) and

Below

40ºF

(4.4ºC) and

Above

DETERMINING CHARGE METHOD

A

B

C

D

E

Figure 34. Determining Charge Method

Summary of Contents for Elite XC13

Page 1: ...Supersedes 07 09 Table of Contents Shipping and Packing List 1 XC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 4 Removing Existing Out...

Page 2: ...ONNECTION 4 1 4 108 4 3 4 121 1 25 2 51 SIDE VIEW C B A 3 1 4 83 UNIT SUPPORT FEET XC13 036 TO 060 BASE SECTIONS WITH ELONGATED LEGS SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW PARTS ARRAN...

Page 3: ...rging Procedures step 1 for a typical manifold gauge connection setup Manifold gauge sets used with HFC 410A refrigerant systems must be capable of handling the higher system operating pressures The g...

Page 4: ...s With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in f...

Page 5: ...overy machine to recover any refrigerant left in the indoor coil and line set Perform the following task 1 Start the existing HCFC 22 system in the cooling mode and close the liquid line valve 2 Pump...

Page 6: ...small base unit stability anchor unit to slab as described in Stabilizing Small Base Unit on Uneven Surfaces ELEVATING AND STABILIZING SMALL BASE UNIT Use the following instructions to elevate and st...

Page 7: ...itional adjustments to the level of the unit NOTE Keep the height of extenders short enough to ensure a sturdy installation If it is necessary to extend further consider a different type of field fabr...

Page 8: ...ructures walls ceilings floors the refrigerant lines will not create unnecessary vibration and subsequent sounds Also consider the following when placing and installing a high efficiency air condition...

Page 9: ...CHORED HEAVY NYLON WIRE TIES 8 FEET 8 FEET STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE FLOOR JOIST OR ROOF RAFTER Figure 14 Refrige...

Page 10: ...the pressure down to 1 or 2 psig 6 9 to 13 8 kPa CAUTION Brazing alloys and flux contain materials which are hazardous to your health Avoid breathing vapors or fumes from brazing operations Perform o...

Page 11: ...ice port valve SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT Removing Indoor Unit Metering Device Remove the existing HCFC 22 fixed orifice or TXV from the indoor coil The existing indoor unit HCFC...

Page 12: ...g the System If the original system used HCFC 22 refrigerant then flush the system using the procedure provided in this section HFC 410A refrigerant then proceed to Refrigerant Metering Device Kits IM...

Page 13: ...it enters the recovery machine 3 After all of the liquid refrigerant has been recovered switch the recovery machine to suction recovery so that all of the HCFC 22 suction is recovered Allow the recove...

Page 14: ...o prevent any possibility of water damage properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures TWO P...

Page 15: ...antities Leak Testing the System After the line set has been connected to both the indoor and outdoor units check the line set connections and indoor unit for leaks Use the following procedure to test...

Page 16: ...will void warranty IMPORTANT Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns Use an instrument capable of accurately measuring down to 50 microns Evacuating the...

Page 17: ...gauge hose from the cylinder Open the manifold gauge valves to release dry nitrogen from the line set and indoor unit 6 Reconnect the manifold gauge to vacuum pump turn pump on and continue to evacuat...

Page 18: ...for minimum circuit ampacity amperage minimum and maximum fuse or circuit breaker fusible HACR per NEC Install power wiring and properly sized disconnect switch 1 NOTE Any excess high voltage field w...

Page 19: ...LENGTH AWG INSULATION TYPE LESS THAN 100 30 METERS 18 TEMPERATURE RATING MORE THAN 100 30 METERS 16 35 C MINIMUM WIRE NUTS BLACK 24V CONTROL WIRES YELLOW TIGHTEN WIRE TIE LOW VOLTAGE CONNECTIONS NOTE...

Page 20: ...uch of the moisture as possible as described in Evacuating the System on page 16 4 Use nitrogen to break the vacuum and install a new filter drier in the system 5 Evacuate the system again Then weigh...

Page 21: ...d 24 hours before unit start up to prevent compressor damage as a result of slugging 6 Set the thermostat for a cooling demand Turn on power to the indoor blower and close the outdoor unit disconnect...

Page 22: ...9 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70...

Page 23: ...tures not reliable START Measure outdoor ambient temperature USE WEIGH IN METHOD Weigh in or remove refrigerant based upon line length APP Approach Values F 1 0 C 0 6 1 Connect gauge set as illustrate...

Page 24: ...subcooling SC SAT _____ LIQ _____ SC _____ 11 Compare results with table below Figure 37 Using HFC 410A Subcooling TXV Charge Method MORE or LESS If refrigerant is added or removed verify charge usin...

Page 25: ...indoor coil WB _______ 12 Record outdoor ambient temperature 13 Compare results with table to the left If value is MORE than shown then ADD refrigerant If value is LESS than shown then REMOVE refrige...

Page 26: ...1 409 142 428 145 431 144 448 150 413 141 428 144 431 144 110 43 436 145 456 147 458 146 477 151 438 143 455 146 457 146 115 46 464 147 486 149 487 148 506 153 466 145 483 147 484 148 Temperature of t...

Page 27: ...it s evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air Have your dealer show you the location of the drain line and how to c...

Page 28: ...ped circuit breakers Make sure unit access panels are in place Make sure air filter is clean Write down the unit model number and have it handy before calling OPTIONAL ACCESSORIES Refer to the Lennox...

Reviews: