background image

Page 11

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏ

Figure 10

COMBUSTIBLE

MATERIAL

Radiation Shield Installation

 ELO183DH UNIT

(TOP)

RADIATION

SHIELDS

RADIATION SHIELDS

(SEE NOTE 1)

FLUE

PIPE

UNIT

CABINET

NOTE 1-Radiation shields must be constructed of 24 gauge sheet
metal minimum.
NOTE 2-Radiation shields required when A is less than 9” (229mm).

NOTE 3-Radiation shields should extend from the top of the unit to
the top of the flue pipe.

NON-COMBUSTIBLE 

SPACERS

 ELO183DH UNIT

(FRONT)

(SEE

NOTE 3)

B

A

A

(SEE NOTE 2)

7”

(178 mm)

12”

(305 mm)

1”

(25 mm)

min.

Barometric Draft Control Installation

Install the provided barometric draft control in the flue pipe

at least 12 inches

 beyond the furnace flue outlet to pro­

vide space for flue gas sampling. The barometric draft con­
trol may be installed in either vertical or horizontal sections
of the flue pipe; however, it should be positioned 

no more

than 18” 

beyond the furnace flue outlet. Follow the instruc­

tions packed with the barometric draft control.

Supply & Return Air Plenums 

NOTE - Following these suggestions when installing  sup­
ply and return air plenums.

1. Use sealing strips of fiberglass.

2. In all cases, the plenum should be secured to furnace

or evaporator cabinet with sheet metal screws.

3. Both supply and return air plenums shall be square

and least 18” long. They should be the same dimen­
sion as the furnace opening.

4. If unit is installed in a confined space such as a utility

room where there is no complete return air duct sys­
tem, a return air connection should be run (the same
size as the return air opening) to a location outside the
room containing the furnace.

5. Install supply and return air ducts as desired.

Optional Filter Kit 

An Optional filter kit is available for ELO183DH units. Kit
35K05 is used with ELO183DH-101/114 units, and kit
35K06 is used with ELO183DH-135/150 units. All kits in­
clude the following:

S

2 filters

S

3 rods

S

7 screws

S

1 rack assembly

S

1 panel

ELO183DH Filter Rack Installation

1. Slide filter rack over return duct flanges.

2. Using a scriber through the filter rack mounting holes,

mark seven mounting hole locations in the return end
of the cabinet. See figure 11.

3. Remove filter rack and drill 1/8” diameter holes at the

marked positions.

4. Place filter rack in position again and secure it to the

cabinet using the sheet metal screws provided. Clear­
ance for the screw driver is provided in outside holes
of rack and in filter support angles.

5. Bend the ends of filter rods and hook ends through

holes provided in top and bottom filter support angles.

6. Slide filter between the support angles and the plenum

side for the filter rack. The filter rods hold the filter in
place.

Figure 11

FILTER RACK

FILTER

RETURN
AIR DUCT
(Not Furnished
by Lennox)

OPENING

IN UNIT

(Either Side)

14 (356)

22 (559)

ELO183DH Optional Filter Kit

Oil Supply Line Sizing

Ensure that the restrictions of the piping system, plus any
lift involved, do not exceed the capability of the oil pump.
Use the following guidelines when determining whether to
use a single-or two-stage oil pump.

Summary of Contents for Elite ELO183DH Series

Page 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Page 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Page 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Page 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Page 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Page 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Page 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Page 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Page 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Page 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Page 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Page 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Page 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Page 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Page 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Page 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Page 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Page 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Page 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Page 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Page 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Reviews: