background image

Page 7

Equipment In Confined Space

All Air From Outside

Outlet Ai

r

Inlet A

ir

Water

Heate

r

Chimney

Or Oil

Vent

Figure 3

NOTE-Each air duct opening shall have a free area of at least one
square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour
of the total input rating of all equipment in the enclosure. If the equip­
ment room is located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall have a
free area of at least one square inch (6.4 square centimeters) per
4,000 Btu (1172 W) per hour of the total input rating of all other equip­
ment in the enclosure.

Oil

Furnace

CAUTION

Combustion air openings in the front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may re­
sult in a fire hazard or injury.

CAUTION

The barometric draft control shall be in the same at­
mospheric pressure zone as the combustion air in­
let to the furnace. Deviation from this practice will
cause improper burner operation and may result in
a fire hazard or injury.

Installation

 

When installed, ELO183DH furnaces must be level. If the
furnace is not level, place fireproof wedges or shims be­
tween the low side of the furnace and floor. Make sure the
weight of the furnace is evenly distributed on all four cor­
ners. Strain on sides of the cabinet causing cracking and
popping noises may occur if weight of furnace is not evenly
distributed.

Set the unit in desired location keeping in mind the clear­
ances list in tables 2 and 3. Also keep in mind oil supply
connections, electrical supply, flue connections and suffi­
cient clearance for installing and servicing unit.

ELO183DH series units may be installed in a crawl space
under a house, utility room or in a wide variety of sus­
pended applications.

Horizontal Application

The ELO183DH furnace is shipped from the factory in the
horizontal left hand air discharge application. Air flow may
be reversed to right side discharge or unit may be used as
downflow.

1. Reversing Airflow for Right Hand Discharge

D

Rotate the furnace 180

_

 so that, when facing the

front, the warm discharge is to the right.

D

Remove the nuts in the bracket that hold the burn­
er to the furnace front. Rotate the burner and burn­
er mounting plate 180

_

 and reinstall the nuts.

D

Remove the screws that hold the limit control in
place. Use the provided knockout hole to relocate
the limit control to the top side of the front panel.

2. Installation on Non-Combustible Material

D

Set the furnace on non‐combustible material
(such as concrete blocks, bricks or angle iron).
Install spacer legs, provided with unit, by using the
cabinet screws from each corner of the unit.

D

Use a level to check the level of furnace in at least
two directions. Use shims or non‐combustible ma­
terial. A minimum clearance of 1” must be main­
tained between bottom of furnace and combus­
tible material.

3. Suspended Installation

D

To suspend the furnace, remove knockouts in top
of panel at warm air discharge and at blower panel
(Refer to unit dimensions). Use 3/8” rods cut to de­
sired length.

D

Use one flat washer and two nuts for each rod (a
nut and washer on the inside of unit and the other
“locking” nut on the outside of unit; see figure 4).
Level the unit by adjusting the nuts on the inside of
unit.

ROD

LOCKING
NUT

TOP OF
FURNACE

WASHER

BLOWER COMPARTMENT

DIVISION PANEL

Hanger Rod Installation

Figure 4

NUT

Downflow Application

When installing the ELO183DH in a downflow position and
on combustible flooring, a combustible floor base must be
used. See Unit Dimension illustration.

1.  Rotate the furnace so that return is on top and supply

is on bottom. Refer to table 3 for clearances to com­
bustible flooring.

2. Remove the nuts in the bracket that hold the burner to

the furnace front. Rotate the burner and burner mount­
ing plate 90

_

 and reinstall the nuts.

Summary of Contents for Elite ELO183DH Series

Page 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Page 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Page 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Page 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Page 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Page 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Page 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Page 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Page 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Page 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Page 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Page 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Page 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Page 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Page 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Page 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Page 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Page 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Page 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Page 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Page 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Reviews: