background image

Page 10

13. The vent pipe shall not be connected to a chimney vent

serving a solid fuel appliance or any mechanical draft
system.

14. All unused chimney openings should be closed.

15. All vent pipe run through unconditioned areas or out­

side shall be constructed of factory-built chimney sec­
tions. See figure 9.

16. Where condensation of vent gas is apparent, the vent

should be repaired or replaced. Accumulation of con­
densation in the vent is unacceptable.

17. Vent connectors serving this appliance shall not be

connected into any portion of mechanical draft sys­
tems operating under positive pressure.

18. Keep the area around the vent terminal free of snow,

ice and debris.

Factory‐Built Chimney

BAROMETRIC

CONTROL*
(IN EITHER

LOCATION)

DRAIN FOR
CONDENSATE

FACTORY
BUILT
CHIMNEY

Figure 9

horizontal ap­

plication shown

*Barometric draft control may be installed in either vertical or
horizontal section of flue pipe no less than 12” and no more than
18” from furnace flue outlet.

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a
venting system commonly run with separate appliances,
the venting system is likely to be too large to properly vent
the remaining attached appliances. The following test
should be conducted while each appliance is in operation
and the other appliances not in operation remain con­
nected to the common venting system. If venting system
has been installed improperly, the system must be cor­
rected as outlined in the previous section.

 1 - Seal any unused openings in the common venting

system.

 2 - Visually inspect venting system for proper size and

horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies
which could cause an unsafe condition.

 3 - Insofar as is practical, close all building doors and win­

dows and all doors between the space in which the ap­
pliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliances not con­
nected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom ex­
hausts, so they will operate at maximum speed. Do
not operate a summer exhaust fan. Close fireplace
dampers.

 4 - Following the lighting instruction on the unit, place the

appliance being inspected in operation. Adjust ther­
mostat so appliance will operate continuously.

 5 - Test for spillage using a draft gauge.

 6 - After it has been determined that each appliance re­

maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to its previous condi­
tion of use.

 7 - If improper venting is observed during any of the

above tests, the common venting system must be
corrected.

Flue Connections 

IMPORTANT

When flue pipe is installed at less than minimum
clearance listed in tables 2 and 3, radiation shields
must be installed. See figure 10.

Use 24 gauge or heavier galvanized smoke pipe and fit­
tings to connect furnace to vent. Maintain rise of at least
one inch per foot. Connect flue pipe to chimney using the
least number of elbows and angles possible. Flue pipe or
vent connector must be inserted into but not beyond the
outside wall of the chimney flue. No reduction in diameter
of flue pipe is acceptable. It is best to have flue pipe as
short and direct as possible.

Where two or more appliances vent into a common flue,
the area of the common flue should be at least equal to the
area of the largest flue or vent connector, plus 50% of the
area of any additional flues or vent connectors. Install
barometric draft control (provided) and flue pipe according
to instructions packed with control.

Inspect flue pipe annually. Clean soot or ash from flue pipe,
if necessary. If pipe is rusted, replace.

Summary of Contents for Elite ELO183DH Series

Page 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Page 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Page 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Page 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Page 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Page 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Page 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Page 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Page 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Page 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Page 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Page 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Page 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Page 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Page 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Page 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Page 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Page 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Page 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Page 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Page 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Reviews: