Installing
The fresh/exhaust air hoods have to be opened and secured during commissioning.
The 3 parts of the air hood have to be assembled thanks to M5 screws delivered in the spare part box.
Check the proper position of the black seal on the top of the hood cover.
Wind direction
The prevailing wind has to be taken into account while choosing the machine position on the building roof.
It
’s highly recommended to avoid putting the fresh air hood in the prevailing wind direction to avoid water ingress risks.
If this is not possible please contact us to require specific water droplet strainer in the hood section.
WARNING: the fresh air hood cover can hurt your head if you
don’t pay attention while turning around the unit.
Fit the hygrometric sensor. Only after opening of the fresh air hood, put in front of the air flow the hygrometric sensor.