eNeRGy-IOM-2020.11-EN
•
59
•
REFRIGERATION
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
LP FAULT
Refrigerant charge too low
Measure the superheat and sub-cooling Good
if 5°C<SC<10°C and 5°C<SH<10°C Bad if
SC>10°C and SH too low
Check superheat adjustment and charge unit (a
leak check must be carried out)
In Heat Pump Mode the temperature
difference between T outdoor and Tevap.
(Dew) is too high
5°C < Delta T < 10°C excellent
10°C < Delta T < 15°C acceptable
15°C < Delta T < 25°C too high
If too high check the coils are clean or check coil
internal pressure drop between the liquid line
and the suction line
Good if < 3bar
Too high > 3 bar (coil blocked)
Refrigeration circuit blocked in distribution
Stop the fan and create icing of the coil.
Check all circuits freeze evenly across the whole
surface of the coil
If some parts of the coil do not freeze this could
indicate a problem with the distribution
Liquid line drier blocked. High temperature
difference
Change filter drier
Electronic expansion valve problem
Check the wiring
Low
pressure
shutdown
due
to
ice
accumulation on the batteries
Check the defrost cycles. (cloud supervision
advised)
MAINTENANCE DIAGNOSTIC
MAINTENANCE DIAGNOSTIC
Summary of Contents for E014AH055FM2M
Page 2: ......
Page 5: ...eNeRGy IOM 2020 11 EN 5...