eNeRGy-IOM-2020.12-EN
•
68
•
Task
Operating mode
Monthly
+
Quarterly
+
Half
Yearly
Check economizer
actuator operation
Check all fixings and transmission. Stop the unit using
the control. The fresh air damper must close. Start the
unit, the fresh air damper should open.
Make a forced opening and closure of the motorized
dampers.
|
Check tightness of all
electrical connections
Power down the unit and check and tighten all screws,
terminal and electric connections (including the
terminal boxes)
When turning on the unit, check the deterioration of the
electrical components with a thermal camera, with the
unit working at 100% of its power.
|
Check HP safety switches
Install a pressure gauge HP and check if the safety
switches overall working.
|
Check the value of the
analog sensors
Install the pressure gauge calibrated to check the analog
sensors.
Install a thermometer calibrated to control the sensors.
Check with a calibrated anemometer the flow rate
displayed by CLIMATIC
|
Check the position of all
sensors
Check the position and fastening of all sensors and their
accessories (pressure tapping tube).
•
Check and clean if
necessary all fresh air
grids
Check the fresh air grilles (if fitted). If dirty or damaged,
remove them from unit and clean with high pressure
water cleaner. Refit on unit once clean and dry.
•
Check electric heater
element for excessive
corrosion
Turn off the unit; Pull the electric heater out of the
heater module box and check the resistances of traces
of corrosion; Replace resistance as required;
|
Check anti-vibration
mountings, for wear and
tear.
Visually check anti-vibration mountings on compressors
and centrifugal fan. Replace if damaged.
•
Check Glycol
concentration in the HWC
circuit and/or in the water
condenser circuits
Check the glycol concentration in the pressurized water
circuit. ( a concentration of 30% gives a protection
down to approx.. -15°C) check the circuit pressure
|
Gas burner module check
for corrosion
Pull out the burner to access the tubes
(refer to Gas burner section in the IOM)
|
Sweeping and cleaning the
gas burner
Clean the in-shot burners and the blower wheel lightly
with a brush. Sweep the flue and flue box. Wipe-off the
dust from the housing of the motor. Clean combustion
air inlet louvers Pull-out baffles from the tubes, sweep
the tubes
CHECK FLUE BOX GASKET
|
MAINTENANCE PLAN