ELECTRICAL DATA
STANDARD
Logical Output Board
(2 outputs : 1 freezed, 1 customized)
A 1 - Alarm, General
B 2 - Customized
(choose 1 output between those 5 possibilities°
- Alarm, FilterS
- Alarm, Blower
- Alarm, Compressors
- Alarm, Heaters
- Free, for BMS
Logical Input Board
(4 inputs : 2 freezed, 2 customized)
A 1 - ON/OFF
A 2 - Reset alarm
B 3 & 4 - Customized
(choose, for each input (2) between those 7 possibilities)
- Disable, Compressors & Heaters
- Disable, Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
- Fault contact, Humidifier
- Free, for BMS
HUMIDITY CONTROL OR TCB
Logical Output Board
(4 outputs : 0 freezed, 4 customized)
B 1 to 4 - Customized
(choose, for each input (4) between those 5 possibilities)
- Alarm, Filters
- Alarm, Blower
- Alarm, Compressors
- Alarm, Heaters
- Free, for BMS
Logical Input Board
(4 outputs: 0 freezed, 4 customized)
B 1 to 4 - Customized
(choose, for each input (4) between those 7 possibilities)
- Disable, Compressors & Heaters
- Disable, Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
- Fault contact, Humidifier
- Free, for BMS
Analogue Input Board
(4 outputs: 0 freezed, 4 customized)
B 1 to 4 - Customized
(choose, for each input (4) between those 4 possibilities)
-Override room temp set point 0-10°C (0-10V)
-Override fresh air set point 0-100%
-Free temperature (NTC probe)
-Free relative humidity (4-20mA)
CONTROL variables
A
: Freezed Input / Output
B
: Customized Input / Output
Summary of Contents for Baltic BCK 020
Page 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Page 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Page 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Page 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Page 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Page 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Page 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Page 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Page 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...