Page 46 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
HEATING: gas burner
PRESSURE ADJUSTMENTS ON HONEYWELL
PRESSURE REGULATING VALVE TYPE VK 4125 P
Pressure regulator adjustment with 300mbar gas
supply:
- The Burner must run in High Heat mode for this check.
- Place the tube of the "accurate" manometer on the Inlet
pressure port figure 54 of the Gas Regulating Valve after
having loosened the screw by two turns
- Check and adjust if necessary the valve Inlet pressure to
20 mbar (G20) or 37 mbar for propane (G31) or 25 mbar for
Groningue (G25).
High Heat Injection Pressure Checks
Check and adjust if necessary the valve OUTLET pressure
to 8.4 mbar (G 20) / 31.4 mbar for propane (G31) and
12.3mbar for Groningue (G25).
The out pressure must be measured on the pressure tap
located on the gas injector support bar to avoid the pressure
drop due to the elbow after the valve
Low Heat Injection Pressure Checks
-Carefully disconnect the wire on the coil of the valve as
shown below
- Check and adjust if necessary the Outlet pressure to 3.5
mbar (G20) or 14 mbar for propane (G31) and 5 mbar for
Groningue(G25)
- Reconnect the wires on the coil
- Re-tighten all pressure adjustment screws and nuts.
INLET
PRESSURE
MEASURING
PORT
Fig. 54
Fig. 55
Fig. 56
Fig. 57
Fig. 58
Fig. 59
Fig. 60
Summary of Contents for Baltic BCK 020
Page 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Page 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Page 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Page 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Page 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Page 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Page 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Page 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Page 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Page 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...