96
Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
3000
Maintenance Replace Filter 1 Not Applicable
Reset filter reminder for both
3001
Maintenance Replace Filter 2 Not Applicable
3002
Maintenance
Replace
Humidifier Pad
Not Applicable
Reset Humidifier pad reminder
3003
Maintenance
Replace UV
Bulb
Not Applicable
Reset UV Light reminder
3004
Maintenance
Maintenance
Reminder
Not Applicable
Make service appointment with
dealer and reset reminder
3005
Maintenance
Pure Air
Maintenance
Not Applicable
Make service appointment for Pure
Air maintenance with dealer and
reset reminder
65537
Service
Urgent
Missing Base
•
Base not detected and alarm 65538 has been raised over 30 times.
• Amber LED is displayed on smart hub.
• Mount and wire mag-mount before powering up smart hub.
Automatically clears once is detected
for two seconds.
65538
Information
Only-Dealer
Missing Base
• Base not detected for at least 30 seconds.
• Amber LED is displayed on smart hub.
• Mount and wire mag-mount before powering up smart hub.
Automatically clears once is detected
for two seconds.