83
Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
429
23
Service
Soon/Service
Urgent
OD Inverter
DC Link Low
Voltage
The inverter has detected a DC link low voltage condition
.
•
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC
for 2- and 3-ton models, 250 VDC for 4- and 5-ton models within 30 seconds, the control will
display a moderate code.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
•
An anti-short cycle timer is initiated. If condition occurs 10 times within a 60 consecutive
minutes, system will lock out and display alert code 429 – critical condition.
• The outdoor control anti-short cycle timer will time out and the unit will recycle the demand.
•
Inverter LEDs will flash code 23.
•
Refer to the unit service documentation for detailed troubleshooting procedures. Perform test
function and verify inverter DC link and line input voltage and current. Also check input to filter
board and reactor before replacing inverter board. To perform this test, go to
menu
>
settings
>
advanced settings
>
view dealer control center
>
tests
.
Inverter flash code 23.
The sequence is:
• Red LED: Two Flashes
• Green LED: Three Flashes
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
Troubleshooting Suggestions:
•
Check wire connections (U, V and W) at inverter plug in harness and compressor.
•
Check the resistance of compressor windings. If not in range, replace compressor.
• Check compressor to ground. If ground issue, replace compressor.
• Check input power (Single Phase - 208/ 10%. If out of range, correct main power
issue.
•
Check DC Link voltage and MICOM Sensing voltage. If out of range, replace inverter. if okay,
possible mechanical issue with compressor.
Go to outdoor unit service manual for detail troubleshooting procedures and require values for
testing DC link voltages and various insulation resistance characteristics.
Automatically clears when the
system detects that the issue no
longer exists.